Introduction

(Continued)

Please refer to document S4100-0031 and the other 
documents listed on page 3 for additional information 
concerning the extensive initiating and notification 
features of the 4100U fire alarm control panels. 

Module Bay Description 

Transponder model 4100-9600 

includes a bay 

assembly, a power distribution interface module (PDI), a 
Basic Transponder Interface Module, and an interconnect 
harness. Communications with the host fire alarm control 
panel are via a Remote Unit Interface (RUI) connection 
that allows for up to 2500 ft (762 m) distance. RUI can 
communicate with up to a total of 31 remote devices and 
can be either Style 4 or Style 7 communications. 

Transponder model 4100-9601 

substitutes a Local 

Mode Transponder Module for the Basic Transponder 
Module. 

Optional Expansion Bays

 each include a PDI and 

accept a variety of optional modules (refer to list starting 
on page 4). 

The Battery Compartment

 (bottom) accepts two 

batteries, up to 50 Ah, that can be mounted within the 
cabinet. Battery mounting does not interfere with 
available module space. A power supply with battery 
charger is required for each battery set. 

Packaging Availability 

x

Modules are power-limited (except as noted, such as 
relay modules) 

x

Enclosure are available for either two or three bay 
sizes or for cabinet rack mounting 

x

Boxes and solid doors are available in beige or red 
(ordered separately) 

x

Up to eight close-nippled cabinets can be connected at 
one transponder location (close-nippled is mounted 
within 20 ft (6 m) and with interconnecting wiring 
enclosed in conduit) 

x

Refer to document S4100-0037 for enclosure details 

Local Mode Control Operation 

Default Stand-Alone Operation.

In the event of a 

communications loss with the host fire alarm control 
panel, model 4100-9601 MINIPLEX Local Mode 
Transponders provide fire alarm response default 
operation for its connected devices and appliances per the 
following. 

Input Operation.

 During local mode operation, 

TrueAlarm initiating devices connected to the transponder 
will cause an alarm at their least sensitive alarm threshold.  

x

Photoelectric sensors will alarm at 3.7%/ft smoke 
obscuration 

x

Ionization sensors will alarm at 1.3%/ft obscuration 

x

Heat sensors will alarm at a fixed temperature of 135° F 
(57° C) 

x

TrueAlarm device LEDs will be activated to indicate a 
device in alarm 

Local Mode Control Operation 

(Continued)

Notification Operation.

 Fire alarm conditions reported 

against a fire alarm point type within a transponder in 
local mode will cause all notification appliance circuits in 
that transponder to: 

x

Sound a general alarm temporal pattern horn tone 

x

Activate visible notification appliance circuits 

Local Mode Module Support.

 Local mode operation 

provides support for the following 4100U modules:  

x

System Power Supplies (SPS), Expansion Power 
Supplies (XPS), and Remote Power Supplies (RPS), 
including on-board notification appliance circuits 
(NACs) and expansion signal modules, operated at a 
temporal pattern,  

x

TrueAlert Power Supplies (TPS) including the on-board  
signaling line circuits (SLCs) 

x

IDNet addressable device circuits, including those 
on-board the SPS, IDNet expansion modules, and the 
quad isolator when used for IDNet communications 

x

4100U amplifiers will provide their on-board horn tones 
(500 Hz) at a temporal pattern through their on-board 
amplifier NACs 

Local Mode Operation Module Exclusion.

 Modules 

not listed above but that are listed as compatible with 
MINIPLEX transponders per this document, do not 
interfere with local mode operation but 

are not supported

during local mode operation. 

Local Mode Controller 

Operation.

 During local mode operation, an optional 

Local Mode Controller will indicate status (see illustration 
below) and can be enabled using a keyswitch to perform 
local alarm silence or reset. If alarms occurring during local 
mode are reset using a Local Mode Controller, upon 
restoration of communications, 

those alarms will not be 

sent to the master controller

. If alarms are still present 

upon restoration of communications, then the alarm 
condition will be reported and host fire alarm control panel 
programmed alarm functions will occur. When 
communications are re-established, the local mode 
transponder restores automatically. 

Mounting.

 Local Mode Controllers are mounted on 

three-gang plates, are available in beige or red, and for 
either flush or semi-flush mounting. (See page 7 for 
details). 

Fire Alarm Local Mode Controller

ENABLE

CONTROL

Alarm

Alarm

Silenced

Local
Mode

Active

Power

On

Alarm

Silence

Reset

Local
Mode

Control

See Operating Instruction 579-343

Local Mode Controller Module 

 

S4100-0035-6  4/2005

Summary of Contents for MINIPLEX 4100-9600

Page 1: ...n Off Auto PressACKlocatedunderflashingindicator Repeat operationuntil allevents areacknowledged Localtonew ill silence AB C AC Pow er D E F G H I J K L M N O P Q R SP 0 S T U VW X Y Z ALARMS F ire Al...

Page 2: ...sensors will alarm at a fixed temperature of 135 F 57 C x TrueAlarm device LEDs will be activated to indicate a device in alarm Local Mode Control Operation Continued Notification Operation Fire alar...

Page 3: ...ashing Tone On Press Ala rmSilence How to Reset System Press Sy stemReset Press Ack tosilence tone device ZONE 1 SIG 2 AUX 3 FB 4 IO 5 IDNet 6 P 7 A 8 L 9 NET ADDR 0 DEL Enter C Exit Fire Alarm Ack Pr...

Page 4: ...UL System Power Supply SPS 9 A power supply charger with 250 point IDNet channel 3 Class A B NACs and expansion slot for City Circuit or Alarm Relay option Canadian model has low battery cutout 4 Blo...

Page 5: ...Model Output Voltage 25 VRMS 70 7 VRMS Power Supply Input Listing Description Details 4100 1328 4100 1329 120 VAC 60 Hz UL 4100 1330 4100 1331 120 VAC 60 Hz ULC 4100 1332 4100 1333 220 230 240 VAC 50...

Page 6: ...102 MAPNET II Module 127 point capacity add devices separately Module size 2 Slots Loading per MAPNET II device 1 7 mA Fully loaded module total 470 mA 490 mA 4100 3103 Isolator Module for MAPNET II o...

Page 7: ...20 ft 6 1 m 2 Nine wires required 24 VDC 2 one per LED indicator 4 and one per switch 3 3 Wire size 18 AWG 0 82 mm Expansion Bay Module Loading Reference Description Mounting Transponder Interface Mo...

Page 8: ...r semi flush mounting 6 stud Optional semi flush trim kit reference Front view box outline without door Side view with door attached 2 Bay height 40 1016 mm Doors can be hinged left or right 3 Bay hei...

Reviews: