6
S4100-0035-6 4/2005
Audio Expansion Signal Module and Options
Model
Description
Details and Mounting Reference
4100-5116
Expansion Signal Module; three, 1.5 A Class B
NACs for Audio applications; up to five maximum
per amplifier; NAC rating = 1.5 A, 50 W, or 100
speakers maximum
Converts one NAC input to three NAC outputs; selects between two
inputs; for Flex-35/50 amplifiers only, two input NACs are required; Single
Block module mounts in expansion bay;
Supv = 18 mA; Alarm with 100 W
amplifiers = 52 mA; Alarm with Flex-35/50 amplifiers = 80 mA
4100-1266
Expansion Signal Module NAC Expander; NAC
rating = 1.5 A, 50 W, or 100 speakers max.
Expands module capacity to six, Class B NACs;
Supv = 0.6 mA; Alarm = 60 mA
4100-1267
Expansion Signal Module Class A Adapter; NAC
rating = 1.5 A, 50 W, or 100 speakers max.
Converts 3 Class B, NACs to Class A;
Supv = 0.6 mA;
Alarm = 30 mA
4100-1268
Expansion Signal Module Constant Supervision
Adapter; Converts 3 Class B NACs to Constant
Supervision Class B or Class A NACs; for
25 VRMS or 70.7 VRMS audio
NAC rating = 1.4 A, 50 W, or 100 speakers max.;
Current vs operating voltage:
25 VRMS Supv = 10 mA;
25 VRMS Alarm = 35 mA; 70.7 VRMS Supv = 38 mA;
70.7 VRMS Alarm = 60 mA
These
modules
mount on the
4100-5116;
select one
max. per
4100-5116
as required
General Audio Options
Model
Description
4081-9018 End-of-line resistor harness for 70.7 VRMS NACs; 10 k
:
, 1 W
4100-2320 Audio Bay-to-Bay Interconnection Harness Kit;
order one for each audio bay addition
4100-0637 Audio Box Interconnection Harness Kit;
order one for each close-nippled audio cabinet
Initiating Device Circuits (IDCs)
Model
Description
Size
Supv.
Alarm
4100-5005 Eight zones, Class B
1 Slot
75 mA
195 mA
4100-5015 Eight zones, Class A
1 Slot
75 mA
195 mA
Addressable Interface Modules
Model
Description
Size
Supv.
Alarm
4100-3101 IDNet Module, 250 point capacity
With 250 IDNet devices, add
–
200 mA
250 mA
4100-3104 IDNet Module, 127 point capacity
With 127 IDNet devices, add
–
102 mA
127 mA
4100-3105 IDNet Module, 64 point capacity
With 64 IDNet devices, add
–
51 mA
64 mA
Module without devices
–
75 mA
115 mA
IDNet Modules, Specifications for each capacity;
Module size = 1 Block
Loading per IDNet device
–
0.8 mA
1 mA
Model
Description
Size
Supv.
Alarm
Module without devices
–
270 mA
290 mA
4100-3102
MAPNET II
®
Module, 127 point capacity, add devices separately;
Module size = 2 Slots; Loading per MAPNET II device = 1.7 mA
Fully loaded module, total
–
470 mA
490 mA
4100-3103
Isolator Module
for MAPNET II or IDNet
communications; converts one SLC into four
isolated Class A or Class B outputs; up to two Modules can be connected to one SLC;
NOTE:
Compatible with MAPNET II Remote Isolators only; for quad isolation with IDNet
Remote Isolators, use 4100-3107 IDNet+ Module (refer to data sheet S4100-0046 for
details)
1 Slot
50 mA
50 mA
Relay Modules; Nonpower-Limited
Model
Description
Resistive Ratings
Inductive Ratings
Size
Supv.
Alarm
4100-3202 4 DPDT w/feedback
10 A
250 VAC
10 A
250 VAC
2 Slots
15 mA
175 mA
4100-3204 4 DPDT w/feedback
2 A
30 VDC/VAC
1/2 A
30 VDC/120 VAC
1 Block
18 mA
70 mA
4100-3206 8 SPDT
3 A
30 VDC/120 VAC
1-1/2 A
30 VDC/120 VAC
1 Block
16 mA
200 mA
Current Calculation Notes:
1.
For total supervisory current, add panel module currents to base system value
and
add all external loads panel-powered loads.
2.
For total alarm current, add panel module currents to base system alarm current
and
add all panel NAC loads
and
all external loads
powered from panel power supplies.
120 VAC Models
3.5 A maximum @ 102 to 132 VAC, 60 Hz
Input Power
[System (SPS); Expansion (XPS);
Remote (RPS); TrueAlert Power Supplies (TPS);
and 100 W amplifiers]
220-240 VAC Models
1.75 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
Total Power Supply
Output Rating
9 A total @ nominal 28 VDC,
including module currents and
auxiliary power outputs
Auxiliary Power Tap 2 A maximum @ nominal 28 VDC
Power Supply Output
Ratings
(System,
Expansion, and Remote
Power Supplies)
NACs Programmed
for Auxiliary Power
2 A maximum per NAC, 5 A maximum @ nominal 28 VDC
Output switches to
battery backup
during mains AC
failure or brownout
conditions
Battery capacity range
6.2 Ah to 50 Ah; selectable via programming for batteries below 18 Ah; the SPS is UL
listed for up to 110 Ah battery charging for remotely located batteries
Battery Charger
(System and Remote
Power Supply)
Charger characteristics
and performance
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per
UL Standard 864, to 70% capacity in 12 hours per ULC Standard S527
Operating Temp. Range 32° to 120°F (0° to 49° C)
Environmental
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F (32° C) maximum
MINIPLEX Transponder Product Selection
(Continued)
General Specifications