background image

Simplex, Inc., 5300 Rising Moon Road, Spring

fi

 eld, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616

Lbdman8p.indd (04/11) • © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com

LOAD BANK MANUAL  •  LBD Series  •  page 8 of 16

can be drawn into the air intakes. During 
Load Bank operation insure that air is 
exiting from the exhaust side.

The load branches should be checked 
for blown fuses or opened load resistors. 
To check the fuses or load resistors, 
operate the Load Bank from a balanced 
3-phase source and check the three 
line currents. The three current read-
ings should be essentially the same. 
If a sizeable difference is noted one or 
more load fuses or load resistors may 
have malfunctioned.

EVERY 50 HOURS 
OR 6 MONTHS

Check the tightness of the electrical 
connections. The expansion and con-
traction caused by Load Bank operation 
may result in loose connections. The 
vibrations caused by the generator set 
may also loosen electrical connections. 
If the Load Bank is transported “over 
the road”, the electrical connections 
should be checked for tightness at a 
shorter-than-normal time interval. See 
“Primary Inspection”.

When troubleshooting Load 
Bank systems always remove 
all test source power, fan/con-
trol power, anti-condensation 
heater power, etc.

TROUBLESHOOTING

This section is designed to aid the 
electrical technician in basic Load Bank 
system troubleshooting.  All of the prob-
lems listed can be veri

fi

 ed with a basic 

test meter and/or continuity tester. For 
safety reasons, when troubleshooting 
Load Bank systems always remove all 
test source power, control power, anti-
condensation heater power, etc.

COOLING FAILURE 
INDICATED

1. Over temperature sensor failure

2. Loss of genset exhaust

3. Air restriction (intake or exhaust)

TEST METERS DO NOT 
OPERATE PROPERLY

1. Meter switch failure

2. Meter multiplier resistor inoperative

3. Improper positioning of meter se-

lector switch

4. Current transformer or current 

transformer wiring failure

5. Test meter failure

6. Meter fuses open

SOME LOAD STEPS 
CANNOT BE ENERGIZED

1. Inoperative load step switches

2. Open load step resistor(s)

3. Inoperative load step relays

4. Inoperative load step contactors

5. Open load step fuses

Summary of Contents for LBD Series

Page 1: ...er XXXXX XX XX Model LBD XXX April 2011 The information herein is the property of Simplex Inc and or its subsidiaries Without written permission any copying transmitting to others and other use except...

Page 2: ...rol System 3 Load System 3 PRIMARY INSPECTION 4 INSTALLATION 4 OPERATION 5 Manual 5 Automatic 5 Load Dump 7 COOLING FAILURE SUBSYSTEM 7 MAINTENANCE 7 Each Operation 7 Every 50 Hours or 6 Months 8 TROU...

Page 3: ...s of unloaded operationofdieselenginegenerators Simplex LBD Series Load Banks are intended for use with water cooled engine generator sets equipped with unit mounted radiators These Load Banks are bui...

Page 4: ...Section Control power 120V is supplied to the Load Bank by one of the following methods 1 testsourceviaacontrolpowertrans former 2 test source line to neutral or 3 external source LOAD SYSTEM Simplex...

Page 5: ...nal electrical or mechanicalproblemsduetoreduced clearance 3 Rotateandpushallswitches through all positions to en sure smooth operation 4 Inspect the bottom of crate enclosure for any compo nents that...

Page 6: ...the load steps which are in the On position Trim is achieved by flipping the load steps On and Off whilethe Master Load is in the On position 7 Adjust source voltage and load Monitor as needed AUTOMA...

Page 7: ...eratorloadincreasesabove70kW This establishes a window between 50kW and70kW insideofwhichthePLCtakes no action to change Load Bank Load When total generator load is below 50kW the PLC receives a signa...

Page 8: ...TR contacts 7 4 will close and 7 1 will open Closed OTR contacts 7 4 will illuminate the Over Temperature lamp Open OTR contacts 7 1 will interrupt the power path to the Normal Operation lamp and the...

Page 9: ...ver the road the electrical connections should be checked for tightness at a shorter than normal time interval See Primary Inspection When troubleshooting Load Bank systems always remove all test sour...

Page 10: ...he most accurate source of part numbers for your Load Bank When ordering replacement parts for Simplex Load Banks always consult the Parts Legend drawing When contacting the Simplex Service Department...

Page 11: ...temperature switch FCB Fan circuit breaker Circuit breaker in series with fan control power FCVR Fan control voltage relay Normally energized relay on relay sub panel FM Frequency Meter Monitors freq...

Page 12: ...itch Normally closed switch used to detect fan failure PSI Pounds per square inch PSR Pump Start Relay RML Remote Master Load Relay RR Run relay RS Remote Load Step Relay RTM Running time meter Keeps...

Page 13: ...Multiply the answer of step 3 times the square root of 3 1 732 5 Dividetheanswerofstep 4by1000 The answer is the actual kilowatts of loadbeingappliedbytheLoadBank Single Phase 1 Determine the line cu...

Page 14: ...th the desired amount of kilowatts applied at 1 0 power fac tor The following calculations are used to determine a step kilowatt rating at other than a rated voltage This is accom plished by referenci...

Page 15: ...watts 1 phase Volts x Amps x PF Volts x Amps 1000 1000 3 phase 1 732 x Volts x Amps x PF 1000 Power Factor expressed as decimal Resistive Load Bank PF is 1 0 Amperes 1 phase KW x 1000 KW x 1000 KW kno...

Page 16: ...BS IN LBS 250 1 4 20 Grade 5 dry 8 96 250 1 4 20 Grade 2 dry 5 5 66 312 5 16 Grade 5 dry 17 204 312 5 16 Grade 2 dry 11 132 375 3 8 Grade 5 dry 30 360 375 3 8 Grade 2 dry 20 240 437 7 16 Grade 5 dry 5...

Page 17: ...35 600V 30A 8 AWG 40 T60060 3CR 4 6 AWG 45 600V 60A 2 3 AWG 50 60100 3CR 600V 100A MISCELLANEOUS TERMINALS METERS SWITCHES COILS RELAYS XFORMERS CONNECTION TORQUE SIZE INCH LBS 4 5 6 10 8 19 10 31 1...

Reviews: