12
BATTERY HARNESS
(734-050)
FUSED AT 15 A
HARNESS
734-049
635-852
BATTERY
BLOCK
120 V
NEUT
GND
POWER
DISTRIBUTION
BLOCK
P5
RED
BLACK
BLACK
WHITE
Bulkhead connector
XPS
ASSEMBLY
XPS
P4
If the XPS is being installed in a 4100-2301 Expansion Bay (for non-4100U/4100ES 2975-91xx
Back Boxes),
1.
For DC wiring, connect the battery block (635-852) to the XPS using Harness 734-050. Feed
red and black wires through the side rail to the front of the XPS to prevent wire damage when the
front panel is lowered. Connect the separate red and black wires (with yellow female terminations)
to plugs P4 (black) and P5 (red) on the XPS.
2.
For AC wiring, connect the white and black wires (Harness 734-049) from the 120 V and NEUT
terminal blocks to the connector at the bottom of the XPS assembly, keeping AC wires at least 1
inch away from all other wires. AC power must be kept to the right side of the cabinet, in the non-
power-limited area. The black wire must be closer to the wall at the XPS connection point.
Figure 7. XPS Connection When Mounted in a 4100 Style Box
Step 3. Internal Wiring,
Continued
4100-2301
Expansion Bay
Wiring
firealarmresources.com