7
XPS configuration consists of setting the address switch as described in this section.
The XPS device address is set via DIP switch SW1, which is a bank of eight switches. From left to
right (see Figure 3, below) these switches are designated as SW1-1 through SW1-8. The function
of these switches is as follows:
SW1-1
. This switch sets the baud rate for the internal 4100 communications line running
between the card and the 4100 CPU. Set this switch to ON to communicate.
SW1-2 through SW1-8
. These switches set the card’s address within the 4100 FACP.
Refer to Table 2 for a complete list of the switch settings for all of the possible card addresses.
Note:
You must set these switches to the value assigned to the card by the Panel
Programmer.
FigureTag FD4-772-01
1
8
7
6
5
4
3
2
Figure 3. DIP Switch SW1
Continued on next page
Step 2. XPS Configuration
Overview
Setting the
Address
ON
OFF
DIP Switches SW1-2 through
SW1-8 set the Card Address.
Figure shows an Address of 3.
4100 Comm. Baud
Rate. Switch
(SW1-1)
Must Be Set to
ON
firealarmresources.com