The power distribution module (PDM) connects to the SPS, RPS, or XPS in each bay. One PDM
is used per back box. Use the instructions below to properly connect the PDM to each bay.
1.
Route the black and white AC power wires to the supplied ferrite bead. Loop the wires
twice through the bead as shown in Figure 5.
Figure 5. Loop wires through bead as shown
2.
Wire 120/220/230/240 VAC to the PDM, keeping AC wires at least 1 inch away from all
other wires. AC power must stay in the right side of the cabinet, in the non-power-limited
area.
3.
Connect batteries to P5 on the PDM using Harness 734-015.
Continued on next page
Step 3. Internal Wiring,
Continued
Power Distribution
Module
Connections
TO AC BREAKER
TO PDM