11
4.
Connect the 734-012 Harness (734-013 for 220/230/240 V versions) from the next connector
on the PDM to the first XPS.
Connect the separate red and black wires (with yellow female terminations) to plugs P4
(black) and P5 (red) on the XPS.
Connect the white and black wires, which terminate together in a white snap-on connector, to
the connector at the bottom of the XPS assembly, as shown below. The black wire must be
closer to the wall at the XPS connection point.
5.
Repeat step 4 for the second XPS, if applicable.
P1
P2
P3
P4
P5
Figure 6. XPS/PDM Connection
Step 3. Internal Wiring,
Continued
Power Distribution
Module
Connections
RED WIRE
BLACK WIRE
XPS
ASSEMBLY
HARNESS 734-015
TO 24 V BATTERY
P5
P4
BATTERY
HARNESS
FUSED AT 15 A
GROUND
BACK BOX
GROUND
SCREW
PDM
(566-246)
(or 566-248;
see below)*
HARNESS
(734-012)
(734-013)*
220 VAC
230 VAC
240 VAC
NEUT
50/60 Hz
2 A
566-248
PDM TERMINAL
BLOCK
Additional bulkhead
connector supplied
here with
220/230/240 V
versions
120 V
NEUTRAL
120 VAC
60 Hz, 4 A
FERRITE
BEAD
*
220/230/240 V PART NUMBERS
APPEAR IN ITALICS.
Bulkhead connector