The 4098-9687 Stand Alone Duct Detector can be powered from 24 VDC, 24 VAC, or
120 VAC power sources. Separate terminal block connections are available for the
24 VDC/VAC or the 120 VAC power sources. When the 120 VAC connection is used,
no connections should be made to the 24 VDC/VAC inputs.
Note
: The power sources must originate from a fused power supply listed for fire
protection signaling use, or from the Fire Alarm Control Panel (FACP) power
supply.
Listed below are the electrical specifications for the 4098-9687 Stand Alone Duct
Detector configurations:
24 VDC Power Operation (Figure 2, Page 4)
•
Input Voltage – 20.4 to 32 VDC
•
Standby Current – 40 mA at 24 VDC maximum
•
Alarm Current – 50 mA at 24 VDC maximum
•
Control Contacts - Alarm Relay - Dry SPDT
K1 N.O. (TB2-1), K1 C (TB2-2), K1 N.C. (TB2-3)
Note:
All relay contacts rated 5 amp at 24 VDC/VAC; or 120 VAC resistive
nonpower-limited.
24 VAC Power Operation (Figure 2, Page 4)
•
Input Voltage – 20.4 to 32VAC
•
Standby Current – 100 mA at 24 VAC maximum
•
Alarm Current – 125 mA at 24 VAC maximum
•
Control Contacts - Alarm Relay - Dry SPDT
K1 N.O. (TB2-1), K1 C (TB2-2), K1 N.C. (TB2-3)
Note:
All relay contacts rated 5 amp at 24 VDC/VAC; or 120 VAC resistive
nonpower-limited.
120 VAC Power Operation (Figure 3, Page 5)
•
Input Voltage – 102 to 132 VAC, 60Hz
•
Standby Current – 30 mA at 120 VAC maximum
•
Alarm Current – 40 mA at 120 VAC maximum
•
Control Contacts - Alarm Relay - Dry SPDT
K1 N.O. (TB2-1), K1 C (TB2-2), K1 N.C. (TB2-3)
Note:
All relay contacts rated 5 amp at 24 VDC/VAC; or 120 VAC resistive
nonpower-limited.
Continued on next page
Electrical Specifications
4098-9687 Stand Alone Duct
Detector Housing
firealarmresources.com
Summary of Contents for 4098-9687
Page 2: ...Blank Page firealarmresources com...
Page 4: ...Blank Page firealarmresources com...
Page 6: ...BLANK PAGE Blank Page firealarmresources com...
Page 25: ...Blank page firealarmresources com...
Page 26: ...Blank page firealarmresources com...