background image

14

To properly remove and replace the detector to the base (see Figure 1):

1.

 

Remove power from the Stand Alone Duct Detector.

2.

 

Loosen the four screws that secure the clear plastic cover to the housing base.

3.

 

Insert a small blade screwdriver into the lock release slot in the base. Rotate
the detector counterclockwise to remove it from the base.

4.

 

Remove dust cover from the replacement detector.

5.

 

Insert the detector into the base and rotate until fully seated, continue
rotation until lock has been engaged.

6.

Secure the clear plastic cover to the housing using the four screws (Torque
screw to 8-10 inch-pounds
).

Note

:

An audible “snap” indicates proper contact engagement

.

WARNING:

System will not operate with dust cover in place.

Basic Unit Test

With power applied to the Stand Alone Duct Detector, introduce aerosol using the
553-673 Smoke Detector Aerosol Tester into the Duct Detector through the test
port holes (Figure 1).  Or, place the 553-810 Magnet Tester next to the test
location on the clear Housing Cover (Figure 12).  Observe “ALARM” LED
operation on the detector or the “ALARM” LED and sounder activation at the
4098-9842 Duct Control Station.  Restore normal operation by momentarily
removing power, removing and replacing the detector head after aerosol has been
cleared from its chamber, or by activating the “TEST/RESET” switch at the
4098-9842 Duct Control Station.

With the air handling unit turned on, and all filters and dampers in place, open one of
the test port holes (Figure 1) by removing one of the red covers marked “Test” on the
unit.  Measure the airspeed velocity inside the duct housing using the Alnor
Instrument Co. Air Velocity Meter (Model 8500) or equivalent (not supplied).

Note

:

Refer to manufacturer instructions when performing this test.

Insert the probe in the test opening and measure the airspeed directly in front of the
sampling tube.  Airspeed measured at this point should be 200 fpm or greater.
Airspeed measured at the inlet is typically 40% – 60% of the actual airspeed in the
duct housing.  Any deviation from the recommended installation rules described
previously can cause this measurement to be unreliable.

If the airspeed measurement is less than 200 fpm, then a direct airspeed measurement
should be taken inside the duct.  Airspeed inside the duct should be between 300 fpm
and 4000 fpm (91 to 1220m/min) for proper operation of the smoke detector.

Airspeed below 200 fpm measured inside of the duct detector may indicate a
sampling or exhaust tube obstructed by debris.  Tubes should be inspected and
cleaned as required.

IMPORTANT:

Make sure the test port covers are replaced after testing.

Continued on next page

Installation, 

Continued

Detector Replacement

AC or DC Operation Detector
Testing

Periodic Air Test

firealarmresources.com

Summary of Contents for 4098-9687

Page 1: ...4098 9687 Stand Alone Duct Detector Installation Instructions 574 777 Rev B firealarmresources com...

Page 2: ...Blank Page firealarmresources com...

Page 3: ...E DUCT DETECTOR WHICH IS OFTEN COMPROMISED FOR PRACTICAL REASONS FOR THE REASONS STATED ABOVE THE EFFECTIVENESS OF THE STAND ALONE DUCT DETECTOR CANNOT BE WARRANTEED OR GUARANTEED UNDER NO CIRCUMSTANC...

Page 4: ...Blank Page firealarmresources com...

Page 5: ...ing 14 Periodic Air Test 14 Magnetic Test for Photoelectric Detectors 15 Preferred Method of Testing Smoke Detectors Sensors 16 Air Differential Pressure Test 17 Maintenance 17 Template 18 Table of Co...

Page 6: ...BLANK PAGE Blank Page firealarmresources com...

Page 7: ...silence switch and detector Test Reset switch For detailed information on using smoke detectors in air distribution systems see NFPA 90A and refer to the following excerpt from NFPA 90A Per NFPA 90A...

Page 8: ...GASKET BASE GASKET SMOKE PORT AIR FLOW TEST HOLES CAP PLUG SHIP GROUP 748 518 SEE NOTE PLACE MAGNET HERE TO TEST Note Two 3 4 conduit entries are provided for field wiring connections 12 18 AWG to th...

Page 9: ...ntrol Contacts Alarm Relay Dry SPDT K1 N O TB2 1 K1 C TB2 2 K1 N C TB2 3 Note All relay contacts rated 5 amp at 24 VDC VAC or 120 VAC resistive nonpower limited 24 VAC Power Operation Figure 2 Page 4...

Page 10: ...CTOR REMOVAL OR LOSS OF POWER 4098 9687 STAND ALONE DUCT DETECTOR Figure 2 Wiring the 4098 9687 Stand Alone Duct Detector for 24 VDC or 24 VAC Operation Continued on next page Electrical Specification...

Page 11: ...CONTROLLED TB1 TB2 TB3 TURNS OFF OPEN CONTACTS ON ALARM OR DETECTOR REMOVAL OR LOSS OF POWER Figure 3 Wiring the 4098 9687 Stand Alone Duct Detector for 120 VAC Operation Electrical Specifications Con...

Page 12: ...two seconds Return the Key Switch to the NORMAL position 3 The red ALARM LED turns off and all the control functions return to normal operation Note When the detector is removed from the Stand Alone...

Page 13: ...ist Indicator Mode Power On LED Alarm LED Sounder Control Relay Normal On Off Off Deactivated Alarm All On Missing Detector Head Off On On Trouble Power Fail All Off Activated 4098 9842 Duct Control S...

Page 14: ...s a minimum of six duct widths downstream from bends or inlets Such locations ensure that air flow is non turbulent and that smoke is properly mixed with air in the duct for maximum detector efficienc...

Page 15: ...5 Locate air duct detectors on the downstream side of filters to sense fire in filters However should the filters block sufficient air flow may not be available for proper air duct detector operation...

Page 16: ...the slot tap rubber plug supplied into the trimmed end See Figure 9 TUBE SUPPORT HOLE ONLY FOR DUCTS MORE THAN 3 FEET WIDE INLET TUBE HOLES FACE UPSTREAM OF AIR FLOW EXHAUST TUBE DO NOT INSERT RUBBER...

Page 17: ...lastic Detector Chamber marked MTG Drill the four self tapping screws through the housing plastic and duct sheet metal to secure the duct housing no pre drilling is required Torque screws 10 12 inch p...

Page 18: ...chine screws Note Be sure to securely tighten the 8 machine screws Torque screws 16 18 inch pounds If conduit is required route conduit to the most convenient knockout and secure to the assembly using...

Page 19: ...tions in accordance with the wiring diagrams Figures 2 and 3 prior to attaching accessory to the box 4098 9842 DUCT CONTROL STATION LISTED STEEL DEVICE BOX BY OTHERS ACCESSORY ACTUAL ACCESSORY MAY VAR...

Page 20: ...its chamber or by activating the TEST RESET switch at the 4098 9842 Duct Control Station With the air handling unit turned on and all filters and dampers in place open one of the test port holes Figu...

Page 21: ...tion see Figure 12 indicated by a TEST mark embossed on the cover the visible LED flashes indicating the detector s condition The following are descriptions of what you should see when using the MAG T...

Page 22: ...rt holes Figure 13 by removing the red cover on the duct detector housing Using the extended nozzle on the smoke detector aerosol tester 553 673 spray a 4 second burst of aerosol through the test port...

Page 23: ...be less than 0 015 inches 381 mm of water nor greater than 1 55 inches 39 370 mm of water After testing is completed secure the clear plastic cover to the housing using the four screws Torque screws...

Page 24: ...ION 1 AND 2 TOP DETECTOR PCB DETECTOR PCB DETECTOR PCB DETECTOR PCB POSITION 1 POSITION 3 CUT NOT ALLOWED POSITION 2 Figure 14 Stand Alone Duct Detector Mounting Template Cut and tape Template to the...

Page 25: ...Blank page firealarmresources com...

Page 26: ...Blank page firealarmresources com...

Page 27: ...Blank page firealarmresources com...

Page 28: ...Rev B Simplex Time Recorder Co Simplex Plaza Westminster Massachusetts 01441 0001 U S A 574 777 Simplex International Time Equipment Co LTD Mississauga Ontario Canada firealarmresources com...

Reviews: