Summary of Contents for 4098-9687

Page 1: ...4098 9687 Stand Alone Duct Detector Installation Instructions 574 777 Rev B firealarmresources com...

Page 2: ...Blank Page firealarmresources com...

Page 3: ...E DUCT DETECTOR WHICH IS OFTEN COMPROMISED FOR PRACTICAL REASONS FOR THE REASONS STATED ABOVE THE EFFECTIVENESS OF THE STAND ALONE DUCT DETECTOR CANNOT BE WARRANTEED OR GUARANTEED UNDER NO CIRCUMSTANC...

Page 4: ...Blank Page firealarmresources com...

Page 5: ...ing 14 Periodic Air Test 14 Magnetic Test for Photoelectric Detectors 15 Preferred Method of Testing Smoke Detectors Sensors 16 Air Differential Pressure Test 17 Maintenance 17 Template 18 Table of Co...

Page 6: ...BLANK PAGE Blank Page firealarmresources com...

Page 7: ...silence switch and detector Test Reset switch For detailed information on using smoke detectors in air distribution systems see NFPA 90A and refer to the following excerpt from NFPA 90A Per NFPA 90A...

Page 8: ...GASKET BASE GASKET SMOKE PORT AIR FLOW TEST HOLES CAP PLUG SHIP GROUP 748 518 SEE NOTE PLACE MAGNET HERE TO TEST Note Two 3 4 conduit entries are provided for field wiring connections 12 18 AWG to th...

Page 9: ...ntrol Contacts Alarm Relay Dry SPDT K1 N O TB2 1 K1 C TB2 2 K1 N C TB2 3 Note All relay contacts rated 5 amp at 24 VDC VAC or 120 VAC resistive nonpower limited 24 VAC Power Operation Figure 2 Page 4...

Page 10: ...CTOR REMOVAL OR LOSS OF POWER 4098 9687 STAND ALONE DUCT DETECTOR Figure 2 Wiring the 4098 9687 Stand Alone Duct Detector for 24 VDC or 24 VAC Operation Continued on next page Electrical Specification...

Page 11: ...CONTROLLED TB1 TB2 TB3 TURNS OFF OPEN CONTACTS ON ALARM OR DETECTOR REMOVAL OR LOSS OF POWER Figure 3 Wiring the 4098 9687 Stand Alone Duct Detector for 120 VAC Operation Electrical Specifications Con...

Page 12: ...two seconds Return the Key Switch to the NORMAL position 3 The red ALARM LED turns off and all the control functions return to normal operation Note When the detector is removed from the Stand Alone...

Page 13: ...ist Indicator Mode Power On LED Alarm LED Sounder Control Relay Normal On Off Off Deactivated Alarm All On Missing Detector Head Off On On Trouble Power Fail All Off Activated 4098 9842 Duct Control S...

Page 14: ...s a minimum of six duct widths downstream from bends or inlets Such locations ensure that air flow is non turbulent and that smoke is properly mixed with air in the duct for maximum detector efficienc...

Page 15: ...5 Locate air duct detectors on the downstream side of filters to sense fire in filters However should the filters block sufficient air flow may not be available for proper air duct detector operation...

Page 16: ...the slot tap rubber plug supplied into the trimmed end See Figure 9 TUBE SUPPORT HOLE ONLY FOR DUCTS MORE THAN 3 FEET WIDE INLET TUBE HOLES FACE UPSTREAM OF AIR FLOW EXHAUST TUBE DO NOT INSERT RUBBER...

Page 17: ...lastic Detector Chamber marked MTG Drill the four self tapping screws through the housing plastic and duct sheet metal to secure the duct housing no pre drilling is required Torque screws 10 12 inch p...

Page 18: ...chine screws Note Be sure to securely tighten the 8 machine screws Torque screws 16 18 inch pounds If conduit is required route conduit to the most convenient knockout and secure to the assembly using...

Page 19: ...tions in accordance with the wiring diagrams Figures 2 and 3 prior to attaching accessory to the box 4098 9842 DUCT CONTROL STATION LISTED STEEL DEVICE BOX BY OTHERS ACCESSORY ACTUAL ACCESSORY MAY VAR...

Page 20: ...its chamber or by activating the TEST RESET switch at the 4098 9842 Duct Control Station With the air handling unit turned on and all filters and dampers in place open one of the test port holes Figu...

Page 21: ...tion see Figure 12 indicated by a TEST mark embossed on the cover the visible LED flashes indicating the detector s condition The following are descriptions of what you should see when using the MAG T...

Page 22: ...rt holes Figure 13 by removing the red cover on the duct detector housing Using the extended nozzle on the smoke detector aerosol tester 553 673 spray a 4 second burst of aerosol through the test port...

Page 23: ...be less than 0 015 inches 381 mm of water nor greater than 1 55 inches 39 370 mm of water After testing is completed secure the clear plastic cover to the housing using the four screws Torque screws...

Page 24: ...ION 1 AND 2 TOP DETECTOR PCB DETECTOR PCB DETECTOR PCB DETECTOR PCB POSITION 1 POSITION 3 CUT NOT ALLOWED POSITION 2 Figure 14 Stand Alone Duct Detector Mounting Template Cut and tape Template to the...

Page 25: ...Blank page firealarmresources com...

Page 26: ...Blank page firealarmresources com...

Page 27: ...Blank page firealarmresources com...

Page 28: ...Rev B Simplex Time Recorder Co Simplex Plaza Westminster Massachusetts 01441 0001 U S A 574 777 Simplex International Time Equipment Co LTD Mississauga Ontario Canada firealarmresources com...