Suppression Release Peripheral Application and Installation Instructions
5
Table 3. SRP RAC Wiring Guidelines
MAXIMUM RAC WIRING DISTANCE
Based on a total Drop of 0.6 V
RAC OUTPUT
CURRENT
(Refer to
actuator rating)
DISTANCE
TOTAL LINE
RESISTANCE
18 AWG
16 AWG
14 AWG
12 AWG
0.50 A
74’
118’
188’
300’
1.06
0.75 A
50’
79’
126’
200’
0.71
1.00 A
37’
59’
94’
150’
0.53
1.25 A
30’
47’
75’
120’
0.43
1.50 A
25’
39’
63’
100’
0.35
1.75 A
21’
34’
54’
85’
0.30
2.00 A
19’
30’
47’
75’
0.27
The SRP RAC outputs are designated on the printed circuit board as RAC+ and RAC-.
The SRP RAC must connect to a 2081-9046-coil supervision module, which in turn
connects to a 12 V DC or 24 V DC actuator (see Figure 4). It can also connect to the
maintenance switches listed in Table 4. See Figure 5 for a connections diagram with a
maintenance switch.
All wiring must be 18 AWG (minimum) to 12 AWG (maximum).
Conductors must test free of all grounds.
All wiring is supervised and power limited unless otherwise noted.
Wiring between 2081-9046-coil supervision modules (Yell/Black) is not power limited.
Refer to the 2081-9046 Coil Supervision Module Wiring Instructions (574-437).
Connect 24 V DC actuator as shown, only one 24 V DC actuator per RAC +, - output.
Connect the 12 V DC actuator as shown. Two units must be connected through a
maximum of 20 feet in conduit.
For specific actuator wiring instructions, refer to the manufacturer’s recommendations.
For UL/ULC application, the RAC is a special application circuit, and must only be
used with the actuators listed in Table 5.
The RAC is compatible for use with any FM approved electric release deluge,
pre-action and refrigerated area sprinkler solenoid valve rated 22 watts or less. Refer
to the solenoid valve manufacturer’s product documentation for verification of agency
listings and power requirements.
Maximum alarm current is 2 A.
Earth Fault Detection on RAC is 2 kOhms or less.
Table 4. Maintenance and Abort Switches
PID
Description
2080-9056
Abort Switch Flush
2080-9057
Abort Switch Surface
2080-9067
Abort Switch Style C Flush
2080-9068
Abort Switch Style C Flush
2080-9059
Maint Switch w/Lamp Flush
2080-9060
Maint Switch w/Lamp Surface
Continued on next page
Wiring
Restrictions
Wiring Guidelines