background image

Suppression Release Peripheral Application and Installation Instructions 

 

5

 

 

Table 3.  SRP RAC Wiring Guidelines 

 

MAXIMUM RAC WIRING DISTANCE 

Based on a total Drop of 0.6 V 

 

RAC OUTPUT 

CURRENT 

(Refer to 

actuator rating)

 

DISTANCE 

 

TOTAL LINE 

RESISTANCE 

 

18 AWG 

 

16 AWG 

 

14 AWG 

 

12 AWG 

0.50 A 

74’ 

118’ 

188’ 

300’ 

1.06 

 

0.75 A 

50’ 

79’ 

126’ 

200’ 

0.71 

 

1.00 A 

37’ 

59’ 

94’ 

150’ 

0.53 

 

1.25 A

 

30’ 

47’ 

75’ 

120’ 

0.43 

 

1.50 A

 

25’ 

39’ 

63’ 

100’ 

0.35 

 

1.75 A

 

21’ 

34’ 

54’ 

85’ 

0.30 

 

2.00 A

 

19’ 

30’ 

47’ 

75’ 

0.27 

 

 

The SRP RAC outputs are designated on the printed circuit board as RAC+ and RAC-.  
The SRP RAC must connect to a 2081-9046-coil supervision module, which in turn 
connects to a 12 V DC or 24 V DC actuator (see Figure 4). It can also connect to the 
maintenance switches listed in Table 4. See Figure 5 for a connections diagram with a 
maintenance switch. 

 

 

All wiring must be 18 AWG (minimum) to 12 AWG (maximum). 

 

Conductors must test free of all grounds. 

 

All wiring is supervised and power limited unless otherwise noted. 

 

Wiring between 2081-9046-coil supervision modules (Yell/Black) is not power limited.  
Refer to the 2081-9046 Coil Supervision Module Wiring Instructions (574-437). 

 

Connect 24 V DC actuator as shown, only one 24 V DC actuator per RAC +, - output. 

 

Connect the 12 V DC actuator as shown. Two units must be connected through a 
maximum of  20 feet in conduit. 

 

For specific actuator wiring instructions, refer to the manufacturer’s recommendations. 

 

For UL/ULC application, the RAC is a special application circuit, and must only be 
used with the actuators listed in Table 5. 

 

The RAC is compatible for use with any FM approved electric release deluge,        
pre-action and refrigerated area sprinkler solenoid valve rated 22 watts or less. Refer 
to the solenoid valve manufacturer’s product documentation for verification of agency 
listings and power requirements. 

 

Maximum alarm current is 2 A. 

 

Earth Fault Detection on RAC is 2 kOhms or less.  

 

Table 4.  Maintenance and Abort Switches 

 

PID 

Description 

2080-9056 

Abort Switch Flush 

2080-9057 

Abort Switch Surface 

2080-9067 

Abort Switch Style C Flush 

2080-9068 

Abort Switch Style C Flush 

2080-9059 

Maint Switch w/Lamp Flush 

2080-9060 

Maint Switch w/Lamp Surface 

 

Continued on next page  

 

 
 

 

 

Wiring 
Restrictions 

Wiring Guidelines 

Summary of Contents for 4090-9005

Page 1: ...E and earlier SRPs sensed only normal 10 k EOL and trouble open circuit conditions and revision F and later SRPs sense normal 10 k EOL trouble open circuits and supervisory 16 2 k disconnect switch c...

Page 2: ...226 242 1100 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 0010 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 0110 6...

Page 3: ...ur supplied nuts do not over tighten 2 The SRP has an optional communications LED option kit 4090 9812 that mounts to the cover If using the LED option kit remove the plastic snap in plug on the enclo...

Page 4: ...0 6 V minimum SRP output coil supervision module minimum actuator voltage 21 7 7 20 4 at the rated actuator operating current including the coil supervision module See Table 3 for maximum RAC wiring...

Page 5: ...on modules Yell Black is not power limited Refer to the 2081 9046 Coil Supervision Module Wiring Instructions 574 437 Connect 24 V DC actuator as shown only one 24 V DC actuator per RAC output Connect...

Page 6: ...A107 097617 005D coil in NPS 5 8 in orifice T8210A107 097617 005D coil in NPS 5 8 in orifice Hygood TSP Model 304 205 010 Electrical Actuator Suppression diode Model 304 209 001 Electrical Actuator Br...

Page 7: ...B YEL COIL SUPERVISION MODULE 2081 9046 LOCATED IN VALVE JUNCTION BOX RAC RAC IDNET IDNET TB3 TB1 TB2 RAC RAC TB1 TB3 TB2 IDNET IDNET P1 Red Black P1 Red Black Notes 1 Refer to Table 3 for maximum RA...

Page 8: ...luding supervision module 0 6 V Drop per Releasing Appliance Circuit RAC Output Interface description is on page 5 and Table 3 RAC wiring is class B only 3 When connecting two IDNet wires to one termi...

Page 9: ...ort operation by following the programming details in the applicable manual When the abort switch is activated the control panel halts the release or discharge of extinguishing agent Pressing and hold...

Page 10: ...pliances The RAC is compatible for use with any FM approved electric release deluge pre action and refrigerated area sprinkler solenoid valve rated 22 watts or less Refer to the solenoid valve manufac...

Reviews: