background image

4090-9005, -9006 

Suppression Release Peripheral 

Application and Installation Instructions 

 2008-2017 Tyco Fire Protection Products. All rights reserved. 

Specifications and other information shown were current as of publication and are subject to change without notice. 
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. 

 

579-385 

Rev. N

 

 

READ AND SAVE THESE INSTRUCTIONS.

  Follow the instructions in this 

installation manual.  These instructions must be followed to avoid damage to this product 
and associated equipment.  Product operation and reliability depend upon proper 
installation. 
 

DO NOT INSTALL ANY SIMPLEX

®

 PRODUCT THAT APPEARS DAMAGED.

  

Upon unpacking your Simplex product, inspect the contents of the carton for shipping 
damage.  If damage is apparent, immediately file a claim with the carrier and notify an 
authorized Simplex product supplier.   

 

ELECTRICAL HAZARD

 Disconnect electrical field power when making any internal 

adjustments or repairs.  All repairs should be performed by a representative or authorized 
agent of your local Simplex product supplier. 

 
 

STATIC HAZARD.

  

Static electricity can damage components. Handle as follows: 

 

Ground yourself before opening or installing components. 

 

Prior to installation, keep components wrapped in anti-static material at all times. 

 

 

When the Suppression Release Peripheral (SRP) is used for field replacement, no action is 
necessary. In a new installation, the software limitations in Table 1 must be adhered to. 
This is because revision E and earlier SRPs sensed only normal (10 k EOL) and trouble 
(open-circuit) conditions, and revision F and later SRPs sense normal   (10 k EOL), 
trouble (open-circuits), and supervisory (16.2 k disconnect switch) conditions. When 
adding a SRP to an existing (pre-revision F) installation, it is necessary to either upgrade 
the software or clip the 16.2 k resistor from the maintenance switches 

 

Table 1. SRP Compatibility Information 

4010 

- SRP is compatible with 4010 IDNet and NACs 
- Master software is at revision 4.01* or higher 
- SFIO software is at revision 4.01* or higher 

4009 

- SRP is compatible with 4009 IDNet and NACs 

4100U 

- SRP is compatible with 4100 IDNet and NACs on the following: 
  SPS,RPS, XPS and XNAC (not XSIG) 
- Master software is at revision 11.11* or higher 
  SPS is at revision 3.07* or higher 
- IDNET and IDNET+ are at revision 3.07* or higher 

4007ES and 4007ES Hybrid 

- Software Revision  3.03 or higher 

4010ES 

- All revisions 
- SRP is compatible with IDNet or IDNet2 and MSS(I) or ESS 

4100ES 

- All revisions 
- SRP is compatible with IDNet or IDNet2 and SPS, or EPS, or RPS, or  
   XPS, or XNAC (all software revisions). 
- SRP is not compatible with XSIG 

* These revisions incorporate the capability to interpret the additional line condition, which is the 
  16.2 k supervisory resistor. 

 

 

This publication describes the installation procedure for the 4090-9005 and 4090-9006 
SRP. The SRP controls the actuator that activates the suppression release systems (such as 
CO

2

 or INERGEN), single or double interlock preaction sprinkler systems, and deluge 

sprinkler systems. 

 

With the SRP, you can upgrade the FACP to enable it to become an agent release system,  
see Figure 1. Appropriate software is required. 

Continued on next page

 

Cautions and 
Warnings 

Important Compatibility 
Information 

Introduction 

 

 

 

Summary of Contents for 4090-9005

Page 1: ...E and earlier SRPs sensed only normal 10 k EOL and trouble open circuit conditions and revision F and later SRPs sense normal 10 k EOL trouble open circuits and supervisory 16 2 k disconnect switch c...

Page 2: ...226 242 1100 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 0010 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 0110 6...

Page 3: ...ur supplied nuts do not over tighten 2 The SRP has an optional communications LED option kit 4090 9812 that mounts to the cover If using the LED option kit remove the plastic snap in plug on the enclo...

Page 4: ...0 6 V minimum SRP output coil supervision module minimum actuator voltage 21 7 7 20 4 at the rated actuator operating current including the coil supervision module See Table 3 for maximum RAC wiring...

Page 5: ...on modules Yell Black is not power limited Refer to the 2081 9046 Coil Supervision Module Wiring Instructions 574 437 Connect 24 V DC actuator as shown only one 24 V DC actuator per RAC output Connect...

Page 6: ...A107 097617 005D coil in NPS 5 8 in orifice T8210A107 097617 005D coil in NPS 5 8 in orifice Hygood TSP Model 304 205 010 Electrical Actuator Suppression diode Model 304 209 001 Electrical Actuator Br...

Page 7: ...B YEL COIL SUPERVISION MODULE 2081 9046 LOCATED IN VALVE JUNCTION BOX RAC RAC IDNET IDNET TB3 TB1 TB2 RAC RAC TB1 TB3 TB2 IDNET IDNET P1 Red Black P1 Red Black Notes 1 Refer to Table 3 for maximum RA...

Page 8: ...luding supervision module 0 6 V Drop per Releasing Appliance Circuit RAC Output Interface description is on page 5 and Table 3 RAC wiring is class B only 3 When connecting two IDNet wires to one termi...

Page 9: ...ort operation by following the programming details in the applicable manual When the abort switch is activated the control panel halts the release or discharge of extinguishing agent Pressing and hold...

Page 10: ...pliances The RAC is compatible for use with any FM approved electric release deluge pre action and refrigerated area sprinkler solenoid valve rated 22 watts or less Refer to the solenoid valve manufac...

Reviews: