background image

FM System Requirements 

 

579-385 

 Rev. N 

 

This section describes specific requirements for Factory Mutual agent release and 
preaction/deluge systems. 
 

 

Use battery calculations for battery voltage to 23 V DC minimum. 

 

Use Coil Supervision Module 2081-9046 on each releasing circuit. 

 

Release circuit voltages must remain between 20.4 V DC and 26.4 V DC under all 
load conditions. Follow wiring chart to determine maximum wiring distance from 
panel to releasing appliances. 
 

 

The RAC is compatible for use with any FM approved electric release deluge, 
pre-action and refrigerated area sprinkler solenoid valve rated 22 watts or less. 
Refer to the solenoid valve manufacturer’s product documentation for 
verification of agency listings and power requirements. 

 

Initiating device circuits must be wired Class A. 

 

Battery standby must be 90 hours. 

 

Release circuit voltages must remain between 20.4 V DC and 26.4 V DC under 
all load conditions. Refer to Table 3 to determine maximum wiring distance 
from panel to releasing appliances. 

Introduction 

General 

Automatic 
Extinguishing 
Release 
Requirements 

Preaction/Deluge 
Applications 

Summary of Contents for 4090-9005

Page 1: ...E and earlier SRPs sensed only normal 10 k EOL and trouble open circuit conditions and revision F and later SRPs sense normal 10 k EOL trouble open circuits and supervisory 16 2 k disconnect switch c...

Page 2: ...226 242 1100 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 0010 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 0110 6...

Page 3: ...ur supplied nuts do not over tighten 2 The SRP has an optional communications LED option kit 4090 9812 that mounts to the cover If using the LED option kit remove the plastic snap in plug on the enclo...

Page 4: ...0 6 V minimum SRP output coil supervision module minimum actuator voltage 21 7 7 20 4 at the rated actuator operating current including the coil supervision module See Table 3 for maximum RAC wiring...

Page 5: ...on modules Yell Black is not power limited Refer to the 2081 9046 Coil Supervision Module Wiring Instructions 574 437 Connect 24 V DC actuator as shown only one 24 V DC actuator per RAC output Connect...

Page 6: ...A107 097617 005D coil in NPS 5 8 in orifice T8210A107 097617 005D coil in NPS 5 8 in orifice Hygood TSP Model 304 205 010 Electrical Actuator Suppression diode Model 304 209 001 Electrical Actuator Br...

Page 7: ...B YEL COIL SUPERVISION MODULE 2081 9046 LOCATED IN VALVE JUNCTION BOX RAC RAC IDNET IDNET TB3 TB1 TB2 RAC RAC TB1 TB3 TB2 IDNET IDNET P1 Red Black P1 Red Black Notes 1 Refer to Table 3 for maximum RA...

Page 8: ...luding supervision module 0 6 V Drop per Releasing Appliance Circuit RAC Output Interface description is on page 5 and Table 3 RAC wiring is class B only 3 When connecting two IDNet wires to one termi...

Page 9: ...ort operation by following the programming details in the applicable manual When the abort switch is activated the control panel halts the release or discharge of extinguishing agent Pressing and hold...

Page 10: ...pliances The RAC is compatible for use with any FM approved electric release deluge pre action and refrigerated area sprinkler solenoid valve rated 22 watts or less Refer to the solenoid valve manufac...

Reviews: