Suppression Release Peripheral Application and Installation Instructions
2
Figure 1. Suppression Release Peripheral
Note:
The IDNet channel supports address codes 1 through 250.
Each SRP has a unique address. The address of the SRP is set with an eight position dip
switch (Figure 1), DIP switch position 1 is the least significant bit (LSB) and position 8 is
the most significant bit (MSB). Set the address using Figure 2 as reference. Use a small
screwdriver or pen to set the switches. Write the
device address for the SRP on the re-
sealable label, this information aids in troubleshooting the system.
Note:
DIP switch in
1
position is
ON
while DIP switch in
0
position is
OFF
.
FigureTag FD9-385-01
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000
0
16
32
48
64
80
96
112
128
144
160
176
192
208
224
240
1000
1
17
33
49
65
81
97
113
129
145
161
177
193
209
225
241
0100
2
18
34
50
66
82
98
114
130
146
162
178
194
210
226
242
1100
3
19
35
51
67
83
99
115
131
147
163
179
195
211
227
243
0010
4
20
36
52
68
84
100
116
132
148
164
180
196
212
228
244
1010
5
21
37
53
69
85
101
117
133
149
165
181
197
213
229
245
0110
6
22
38
54
70
86
102
118
134
150
166
182
198
214
230
246
1110
7
23
39
55
71
87
103
119
135
151
167
183
199
215
231
247
0001
8
24
40
56
72
88
104
120
136
152
168
184
200
216
232
248
1001
9
25
41
57
73
89
105
121
137
153
169
185
201
217
233
249
0101
10
26
42
58
74
90
106
122
138
154
170
186
202
218
234
250
1101
11
27
43
59
75
91
107
123
139
155
171
187
203
219
235
0011
12
28
44
60
76
92
108
124
140
156
172
188
204
220
236
1011
13
29
45
61
77
93
109
125
141
157
173
189
205
221
237
0111
14
30
46
62
78
94
110
126
142
158
174
190
206
222
238
15
31
47
63
79
95
111
127
143
159
175
191
207
223
239
LSB
MSB
1
2
3
4
5
6
7
8
1111
DIP SWITCHES 5 THRU 8
ON
OFF
1 = ON
0 = OFF
251
252
253
254
255
DIPSWITCH IS SHOWN SET AT ADDRESS 7.
Figure 2. Suppression Release Peripheral
Address Chart
Introduction
Setting the SRP
Address
ADDRESS SWITCH
(SW1)
BRACKET
ASSEMBLY
SUPPRESSION
RELEASE MODULE
RAC OUTPUT
(TB2)
NAC INPUT
(TB1)
LED HARNESS
PLUG (P1)
IDNet INPUT
(TB3)