8.8
Printing Reports
The system can generate any of the following reports.
Table 5: System reports
Report
Description
Alarm History Log Report
Report includes all information contained in the alarm history log - device, custom
label, time and date device entered alarm.
Trouble History Log Report
Report includes all information contained in the trouble history log - device, custom
label, type of trouble, time and date device experienced trouble.
TrueAlarm Status Report
Reports the following information for each point.
• Device
• Custom Label
• Current Sensitivity of the Point
• Point Status: Normal, Trouble, Alarm
• Almost Dirty Status: Points which are almost dirty have an asterisk in this field to
denote this.
TrueAlarm Service Report
Reports the following information for each point.
• Device
• Custom Label
• Alarm Level (sensitivity level of the device)
• Average Value
• Current Value
• Percent of Alarm: Shows the current value for the sensor. Value is shown as
a percentage of 100 per- cent (alarm). For example, if the value shown is 9%,
it means that the sensor is currently at 9% of the value required to trigger an
alarm.
• Peak Value. Shows the highest value that the sensor has reached. Value is shown
as a percentage of 100 percent (alarm). For example, if the value shown is 9%,
it means that the peak value experienced by the sensor was 9% of the value
required to trigger an alarm.
• Current State: Possible values include Normal, Trouble, Dirty, Excessively Dirty,
and Almost Dirty.
8.8.1 Procedure for report printing
1.
Press the MENU key. Use the NEXT and PREVIOUS keys to scroll through the choices until the "REPORTS" choice is displayed.
Press ENTER.
2.
Use the NEXT and PREVIOUS keys to scroll through the categories of report (e.g., Alarm History or Trouble History).
3.
When the category of report you want to print is displayed, press ENTER. The system prompts you to confirm that you want to
generate the report. Press ENTER again.
The report prints on the panel's report printer.