background image

5.5     Individually Acknowledging Troubles

When individual acknowledge is used, the tone-alert re-sounds when the condition clears. Individual acknowledge must be selected if the

panel is providing proprietary receiving service in accordance with NFPA 72. Follow these steps to use individual acknowledge:

1.

Unlock and open the enclosure door. The display shows the trouble condition. For example:

Figure 20: Trouble Display

2.

Press the TROUBLE ACK key. An alarm list opens. Every flashing report indicates an unacknowledged trouble condition. Continue

pressing the TROUBLE ACK key and read- ing the reports until all reports have been acknowledged. Once all reports have been

acknowledged the tone-alert silences and the LED glows steady.

3.

Read the display. Investigate the trouble to determine its cause. Make necessary repairs in accordance with the manufacturer's

instructions. When the trouble clears, the Trouble LED flashes and the tone-alert sounds steady.

4.

Press the TROUBLE ACK key. The display shows the system status. Press the TROUBLE ACK key again. After a delay, the display

shows that the system status is normal.

5.6     If the Trouble Doesn't Clear

On global acknowledge systems, trouble points do not usually require acknowledgment of the cleared condition. If the system does

not clear, read the display. The information on the display will indicate the circuit or nature of the fault. Some faults interfere with the

protection provided by the Fire Alarm system. If the source of the trouble cannot be located, call an authorized Simplex representative to

repair the system.

5.6.1     System Reset Key

Some troubles latch until they are reset manually, or are reset by pressing the SYSTEM RESET key. Try pressing the SYSTEM RESET key if the

trouble is any one of the following:

• Class A initiating device circuit trouble
• City Circuit trouble
• 24 Point I/O trouble

If pressing the SYSTEM RESET key does not clear the trouble, or if the trouble toggles (clears and then reappears), the indicated circuit

should be checked by a qualified service technician.

5.7     Trouble Conditions

Trouble Indications for TrueAlarm Sensors

TrueAlarm devices are considered sensors instead of detectors because these devices do not determine alarm conditions. Instead,

the TrueAlarm smoke sensor is a measuring device that sends data regarding smoke density to the FACP. The TrueAlarm heat sensor

operates in a similar fashion, but it sends temperature data to the control panel instead of smoke density data. The FACP uses this data to

determine whether a trouble has occurred.
The TrueAlarm sensor has two automatic trouble indications. Either condition requires service by a qualified service technician.

• 

Dirty

. A "Smoke Detector Dirty" condition is reported any time the average value on an individual sensor reaches a set threshold

value. The sensor continues to operate at the programmed alarm threshold.

• 

Excessively Dirty

. A "Smoke Detector Excessively Dirty" trouble condition is reported any time the average value of an individual

sensor reaches a level such that full-range alarm detection is compromised. When a sensor is “excessively dirty,” the sensor will be

susceptible to false alarms.

In addition to the two automatic trouble conditions, the FACP software includes a pre-programmed digital pseudo point (P132, Sensor

Almost Dirty Log Enable) that can be selected through the ES Panel Programmer application. When selected, a system log entry is

page 17

579-685  Rev. D

InfoAlarm Operator’s Manual 4100U, 4100ES, 4010ES

Summary of Contents for 4010ES

Page 1: ...579 685 Rev D 0579685D InfoAlarm Operator s Manual 4100U 4100ES 4010ES...

Page 2: ...This page is intentionally blank...

Page 3: ...System Reset Key 17 5 7 Trouble Conditions 17 5 7 1 What to Do when TrueAlarm Troubles Occur 18 6 Supervisory Conditions 19 6 1 How the FACP Indicates the Presence of a Supervisory Condition 19 6 1 1...

Page 4: ...10 1 Single channel audio operation 31 10 2 Single Channel Audio Plus Paging 32 10 3 Two Channel Audio Operation 34 10 4 Three to Eight Channel Audio System Operation 37 page ii 579 685 Rev D InfoAla...

Page 5: ...NS PART 15 This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protecti...

Page 6: ...n the screen When describing the action of the softkey the following convention is used Figure 1 LCD with Softkeys Cutaway Table 1 Conventions Convention Meaning title softkey Indicates the softkey be...

Page 7: ...on 4100U audio evacuation messages when an initiating point activates It monitors and controls auxiliary building equipment fan dampers relays security devices Note The term point is used extensively...

Page 8: ...notification appliances horns The LED indicates when this key has been used System Reset Key Pressing this key directs the panel to reset all attached devices and clear all acknowledged alarms troubl...

Page 9: ...he multi line LCD shows either a text screen indicating normal operation see Figure 3 or a sitemap see Figure 4 Figure 3 Normal Operation Text Screen Figure 4 Normal Operation Sitemap Screen Note If t...

Page 10: ...system display is enabled There are six ways that InfoAlarm can display an alarm 4 2 1 How the FACP Indicates that an Alarm has Occurred The following display options are available for all alarm Prior...

Page 11: ...on for the new unacknowledged alarm appears over the neighboring icon Refer to 579 849 ES Panel Programmer s Manual for instructions on allocating site point coordinates Figure 8 Sitemap Display Direc...

Page 12: ...Global acknowledge When global acknowledge is enabled one press of the ALARM ACK key acknowledges every abnormal point currently reporting an alarm status This is helpful when a series of devices ent...

Page 13: ...larm Continue to do this to review all alarms in the system 4 2 4 Individually Acknowledging Alarms Use the following procedure if the Individual Acknowledge option is enabled on your FACP system 1 Un...

Page 14: ...s for a short time to indicate the action was not taken The message ALARM SILENCE NO LONGER INHIBITED displays when the timer expires If Waterflow Sprinkler Devices are activated notification applianc...

Page 15: ...r device remains in alarm and fails to reset the SYSTEM RESET IN PROGRESS message is followed by the message shown below Figure 17 Alarm Present Information Box When this message appears the system re...

Page 16: ...IDNet or RUI channel after the problem causing the trouble is resolved If you attempt to perform a hardware reset without first fixing the problem causing the trouble the hardware reset fails and the...

Page 17: ...First Last Display for Trouble Condition 5 3 What an Acknowledge Does The first step in managing a trouble condition is to acknowledge the trouble Acknowledging a trouble does two important things It...

Page 18: ...open the enclosure door The display shows the trouble condition For example Figure 19 Trouble Display 2 Press the TROUBLE ACK key under the flashing yellow LED The display shows a list of all devices...

Page 19: ...lly or are reset by pressing the SYSTEM RESET key Try pressing the SYSTEM RESET key if the trouble is any one of the following Class A initiating device circuit trouble City Circuit trouble 24 Point I...

Page 20: ...nd schedule maintenance cleaning for the sensors Dirty This trouble means that maintenance should be scheduled for the sensor Contact your facilities management personnel to report the trouble and sch...

Page 21: ...wledge is enabled the SUPV ACK key must be pressed to individually acknowledge each supervisory condition Individual acknowledge must be selected if the panel is providing proprietary receiving servic...

Page 22: ...his step and read the reports The display shows the area and type of condition The tone alert silences and the yellow LED glows steady 3 Read the display Investigate the problem to determine its cause...

Page 23: ...s can be selected as follows 1 Press the appropriate acknowledge key to enter the list For example press the FIRE ALARM ACK key to enter the list of current fire alarms or press the TROUBLE ACK key to...

Page 24: ...esents a point and is a number from 1 to n n represents the number of the last I O point in your system IDNet allows you to select an IDNet MAPNET or VESDA point C D where C represents the IDNet MAPNE...

Page 25: ...Enables the selected point Disable Disables the selected point Select Item Displays point information on screen Enter can also be pressed to display the point info to the display Delete Deletes a cha...

Page 26: ...eypad located on the right side of the interface panel 3 Press the direction keys until the cursor highlights Access Press ENTER or the Select Item softkey 4 Scroll the cursor to the Login command and...

Page 27: ...IRE ALARM ACK key to enter the list of active fire alarms b Use the NEXT and PREVIOUS keys to scroll through the list until the alarm in which you are interested is displayed c Press and hold the Even...

Page 28: ...mple if the point is a signal point a setting of AUTOMATIC indicates that the signal is under the control of the job executing on the panel To return the state of a point that is currently ON or OFF t...

Page 29: ...for the sensor Value is shown as a percentage of 100 per cent alarm For example if the value shown is 9 it means that the sensor is currently at 9 of the value required to trigger an alarm Peak Value...

Page 30: ...u activate an initiating device the system s signals pulse a code that allows you to verify exactly which initiating device triggered the signals For hardwired monitor zones the signal code correspond...

Page 31: ...is enabled If the arrow points to NO logging is disabled Press 2 on the keypad to toggle the setting of this option Coding When ZONE is selected the signals play a code that indicates the activated i...

Page 32: ...ation message automatically plays Manually Selected Pre Recorded Messages Some systems are capable of playing a prerecorded message when a specific button is pressed For example you may press a button...

Page 33: ...vided into eight groups each of which represents a floor of the building A single channel audio system can play a pre recorded message or live audio one floor at a time Figure 27 Single Channel Audio...

Page 34: ...Wait for the Ready to Talk LED to illuminate It will not illuminate until the evacuation message has finished playing 3 Speak into the microphone to page the floors being evacuated Page Additional Fl...

Page 35: ...this button illuminates along with the LEDs for each of the speaker circuits 2 Key the microphone depress the talk switch and wait for the Ready to Talk LED to illuminate When this LED is ON talk int...

Page 36: ...on Floor 2 Figure 28 Two Channel Hardware Evacuate Entire Building 1 Press the All Speakers Evac button to play the evacuation message on every speaker circuit connected to the audio system 2 To indic...

Page 37: ...LED associated with the Selective Alert button illuminates and the Alert message plays on the selected speaker circuit Evacuate Floors On Which Alert Message is Playing Follow these steps to convert...

Page 38: ...the Alarm Silence button on the front panel to silence the audio system When you do this the speakers remain on but play nothing Resetting the Audio System Press the System Reset button to reset the a...

Page 39: ...ll Speakers Evac button to play the evacuation message on every speaker circuit connected to the audio system To indicate that the All Speakers Evac function has been activated the LED associated with...

Page 40: ...ated with the Selective Alert button illuminates and the Alert message plays on the selected speaker circuit Evacuate Floors On Which Alert Message is Playing Follow these steps to convert the Alert m...

Page 41: ...being played on the Alert channel at that time The LED associated with this button illuminates when the button is pressed to indicate the function is active Note If the user picks up the local phone o...

Page 42: ...al listings may be applicable contact your local Simplex product supplier for the latest status Listings and approvals under Simplex Time Recorder Co Simplex and the product names listed in this mater...

Reviews: