Addressable notification appliance communications

 

include operation of TrueAlert and TrueAlert ES Visible only 

(V/O, strobe), Audible only (A/O, horn), Audible/Visible (A/V, 

horn/strobe), and strobes of Speaker/Visible (S/V) notification 

appliances. (S/V appliances require separate speaker wiring.) 

IDNAC SLC addressable communications allow each horn and 

strobe to be individually controlled using a single two-wire 

circuit, confirms the wiring connections to the individual 

notification appliance’s electronic circuit, and confirms 

communications between each appliance and the fire alarm 

control panel. Addressable communications increases 

supervision integrity versus conventional notification systems 

by providing supervision beyond the circuit wiring to each 

individual appliance and by constantly verifying the ability of 

each appliance to communicate with the control panel. 

Individual Appliance Status and Settings.

 The fire alarm 

control panel monitors and records each addressable notification 

appliance status, type of appliance, and its configured appliance 

settings. A fault in any individual appliance automatically 

reports a trouble condition to the control panel. 

TrueAlert ES Addressable Appliance Reference 

 

 

A/O (horn) 

V/O (strobe) 

A/V (horn/strobe) 

Virtual NACs Provide Control Convenience.

 For control 

convenience, IDNAC notification appliances can be grouped 

into 

Virtual NACS

 (VNACs) for group control, grouping that 

can be made across SLCs, not defined by their wiring 

connection. 

Panel Control Convenience.

 Applicable operation settings 

for each appliance can be programmed 

without having to 

replace appliances or remove them from the wall or ceiling

. An 

appliance’s VNAC notification zone can be easily changed 

through programming without having to add additional circuits, 

conduit, and wiring. Audible and visible appliances for non-Fire 

Emergency Communications notification can be programmed to 

operate separately 

on the same pair of wires as the fire alarm 

notification appliances

. The result is lower installation, retrofit, 

and overall life-cycle cost of ownership compared with 

traditional conventional notification systems. 

Installation, Retrofit, and Life-Cycle Cost Benefits.

 

With each addressable appliance capable of being controlled 

separately on the same two-wire IDNAC SLC, installation time 

and expense for both retrofit and new construction can be 

significantly reduced. When Class B wiring is used, wiring can 

be “T-tapped” allowing more savings in distance, wire, conduit 

(size and utilization), and overall installation efficiency. 

Location Information, Diagnostics and 

Troubleshooting.

 Each addressable notification appliance 

has its own 40 character custom label to identify the location of 

the appliance and to aid in troubleshooting fault conditions. In 

conventional notification systems, conventional appliances are 

not capable of communicating with the control panel. Fault 

reporting on a conventional system is limited to the circuit 

wiring and the entire area (zone) covered by appliances on the 

notification appliance circuit (NAC) making it much more 

difficult and costly to locate and correct the source of a 

 

problem. Using the TrueAlert 

magnet test

 allows each appliance 

to individually identify its candela setting and address and to 

briefly operate if desired, and using the 

TrueAlert ES 

Appliance Self-Test feature provides detailed performance 

verification per appliance.

  

TrueAlert ES Appliance Self-Test Operation 

 

On-Board Test Sensors.

 TrueAlert ES appliances are 

equipped with on-board sensors to detect strobe and/or horn 

output allowing efficient and unobtrusive Self-Testing. When 

Automatic Self-Test

 is initiated from the control panel, each 

appliance within the selected VNAC group will briefly operate 

and then report its Self-Test status to the control panel, all 

within several seconds. Silent Self-Test can be selected to test 

only visible appliance if desired. The control panel is in a 

trouble condition during testing and in the event of an alarm, 

Self-Test is automatically terminated.

 Additionally, Automatic 

Self-Test can be scheduled

 to occur at a convenient time on a 

regular basis. 

Automatic Self-Test results

 are communicated to the 

control panel with a time and date stamp and are stored in 

memory. Results are viewable at the front panel display and 

printed reports can be generated from the panel service port. 

 

Individual Self-Test

 is selected from the control panel when 

individual appliances need to be observed to operate. Each 

appliance in the selected VNAC group will turn on its LED 

until individually activated by applying a magnet. After 

performing the individual test, the appliance LED turns off to 

indicate completion. Results are recorded the same as during the 

automatic test. 

 

IDNAC SLC Hardware Reference 

 

The Enhanced System Supply 

provides two, 3 A IDNAC 

SLCs for control and power to TrueAlert ES and TrueAlert 

addressable notification appliances. Both power supplies 

incorporate an efficient switching design that provides a 

regulated output of 29 VDC, even during battery operation. 

With 29 VDC minimum output at the panel, addressable 

notification SLCs can support wiring distances 2 to 3 times 

farther than available with conventional notification, or support 

more appliances per SLC, or work with smaller gauge wiring, 

or combinations of these benefits. The result is installation and 

maintenance savings with high assurance that appliances that 

operate during normal system testing will operate during worst 

case alarm conditions.  

IDNAC SLC Appliance Wiring Reference 

 

IDNAC SLC Capacity

: Up to 127 addresses and up to 139 unit 

loads (appliances are typically one unit load, devices such as 
Isolators may require more than one load, refer to individual 
device data sheet for specific information) 

Recommended Wire Type 

UTP, unshielded twisted pair  

Maximum wire length 
allowed with “T-Taps” for 
Class B wiring, per SLC 

10,000 ft (3048 m) 

Maximum wire length per 
SLC to any appliance 

4000 ft (1219 m) 

Appliance Supervisory 
Current 

1 unit load = 0.8 mA per appliance  

Wiring Connections 

Terminals for 20 to 12 AWG 
(0.52 mm

2

 to 3.31 mm

2

 

S4010-0011-5  11/2015

 IDNAC SLC Control of TrueAlert and TrueAlert ES Addressable Notification

 

Summary of Contents for 4010-9601

Page 1: ...either Class B or Class A operation 48 LED panel mount annunciation provides 40 Red and 8 Yellow pluggable LEDs select models meets ULC requirements optional LED kits are available to change individual LED color to Green or Blue to meet specific site requirements Optional ESS mounted modules door mounted modules and other options include City Connect with or without disconnect switches Alarm Relay...

Page 2: ...of the 4010ES ESS There are 3 available 4 x 5 blocks for mounting 4010ES hardware options Other 4010ES Options The 4010ES City Connect module or the optional Alarm Relay module mount directly to the ESS These options are mutually exclusive Network Media modules mount directly to the 4010ES Network Interface Card The TrueInsight Remote Gateway mounts on the back side of the 4010ES User Interface Pa...

Page 3: ... point category and point selection alphabet characters are not used at this time ADDITIONAL FUNCTION KEYS Event Time Request More Information Request Lamp Test Elevator Bypass City Disconnect Ground Fault Waterflow West Waterflow East Custom label insert LCD NAVIGATION CONTROL Menu selection Vertical and Horizontal position selection buttons 2 X 40 LCD READOUT LCD is backlighted during normal con...

Page 4: ...details TrueAlarm heat sensors can be selected for fixed temperature detection with or without rate of rise detection Utility temperature sensing is also available typically to provide freeze warnings or alert to HVAC system problems Readings can selected as either Fahrenheit or Celsius TrueSense Early Fire Detection Multi sensor 4098 9754 provides photoelectric and heat sensor data using a single...

Page 5: ...by appliances on the notification appliance circuit NAC making it much more difficult and costly to locate and correct the source of a problem Using the TrueAlert magnet test allows each appliance to individually identify its candela setting and address and to briefly operate if desired and using the TrueAlert ES Appliance Self Test feature provides detailed performance verification per appliance ...

Page 6: ...epending on model see model selection below for additional details on specific models Cabinet and door 6 A Enhanced System Supply details Two 3 A Class B IDNAC SLCs for up to 254 addressable notification appliances Class A operation is available using the 4010 9930 Dual Class A IDNAC Isolator DCAI module Up to 2 A of auxiliary power 110 Ah UL 50 Ah ULC battery charger 33 Ah maximum in the control ...

Page 7: ...from the list below 2 Vertical Blocks NA NA 4010 9922 Modular Network Interface Card requires two media modules see below 2 Vertical Blocks 30 mA 30 mA 4010 9818 Network Media Card Wired N A mounts to 4010 9922 55 mA 55 mA 4010 9819 Network Media Card Fiber Optic 25 mA 25 mA 4010 9914 Building Network Interface Card 2 Vertical Blocks 236 mA 236 mA 4010 9923 SafeLINC Internet Interface 2 Vertical B...

Page 8: ...representative for more details LED Kits LEDs are pluggable use to change color for local application requirements Model Description 4100 9843 8 Yellow LED Kit 4100 9844 8 Green LED Kit 4100 9845 8 Red LED Kit 4100 9855 8 Blue LED Kit End User Programming Tools Model Description 4100 8802 End User Programming Unit Software 4100 0292 Custom Label Editing USB Dongle 4100 0295 Port Vectoring Setup an...

Page 9: ...iator English 1 4606 9102CF 4010ES RUI LCD Annunciator French 1 for Canada 4602 9101 Status Command Unit SCU LED Annunciator 1 4602 9102 Remote Command Unit RCU LED Annunciator w control 1 4602 9150 Graphic I O RCU SCU Assembly for custom annunciator panels 1 4602 7101 Graphic I O RCU SCU Assembly for custom annunciator panels 1 4602 7001 RCU for cabinet mount 1 4602 6001 SCU for cabinet mount 1 4...

Page 10: ...ence Installation Instructions 579 1150 Operating Instructions 579 969 Subject Data Sheet Subject Data Sheet 4010ES Agent Release Applications and Accessories S4010 0005 Network Communications S4100 0056 Agent Release Accessories S2080 0010 Multi Signal Fiber Optics S4100 0049 Building Network Interface S4100 0061 4602 Series SCU RCU S4602 0001 SafeLINC Internet Interface S4100 0062 PC Annunciator...

Reviews: