Features 

 

4010ES Agency listings: 

 

UL 864, Fire Detection and Control (UOJZ), and 
Smoke Control Service (UUKL), and Releasing 
Service (SYZV) 

 

UL 2017, Process Management Equipment (QVAX) 

 

UL 1076, Proprietary Alarm Units-Burglar (APOU) 

 

UL 1730, Smoke Detector Monitor (UULH) 

 

ULC S527-99, Fire Detection and Control (UOJZC) 

 

ULC S559-04, Supervising Station (DAYRC) 

Introduction 

 

4010ES Series Fire Detection and Control Panels

 

provide leading edge installation, operator, and service 
features for customer applications in the mid-range 
addressable fire alarm systems market. An on-board 
Ethernet port provides fast external system 
communications to expedite installation and service 
activity. Dedicated compact flash memory archiving 
provides secure on-site system information storage of 
electronic job configuration files to meet NFPA 72 
(

National Fire Alarm and Signaling Code

) requirements.  

Modular design.

 A variety of functional modules are 

available to meet specific system requirements. Selections 
allow panels to be configured for either Stand-Alone or 
Networked fire control operation.  

 Mechanical Description  

 

 

Mounting box provides convenient stud markers for 

drywall thickness and nail-hole knockouts for quicker 

mounting  

 

Smooth box surfaces are provided for locally cutting 

conduit entrance holes exactly where required 

 

The hinged User Interface panel easily opens for 

internal access 

 

Modules are power-limited (except as noted, such as 

relay modules) 

 

Doors include tempered glass inserts, boxes and doors 

are available in platinum or red  

 

Box and door/retainer assemblies are included with 

Basic Panel assemblies 

 

Cabinet assembly is rated NEMA 1 and IP 30 

 

Cabinet assembly design has been seismic tested and 

is certified to IBC and CBC standards as well as to 

ASCE 7 categories A through F, requires battery 

brackets as detailed on data sheet S2081-0019  

 

Panel Hardware  

 

4010ES Block Space Option Cards

 mount to the left 

of the 4010ES ESS. There are 3 available 4” x 5” blocks 
for mounting 4010ES hardware options. 

Other 4010ES Options:

 The 4010ES City Connect 

module or the optional Alarm Relay module mount 
directly to the ESS. These options are mutually exclusive.  

Network Media modules mount directly to the 4010ES 
Network Interface Card.  

The TrueInsight Remote Gateway mounts on the back 
side of the 4010ES User Interface Panel. 

The Battery Compartment

 located in the bottom of 

the 4010ES cabinet accepts two batteries, up to 33 Ah, 
without interfering with expansion module space.  

The illustrations at the bottom of this page identify 
mounting locations available for optional 4010ES 
modules. (refer to page 7 for additional information) 

Software Feature Summary  

 

 

TrueAlarm individual analog sensing with front panel 
information and selection access 

 

“Dirty” TrueAlarm sensor maintenance alerts, service 
and status reports including “almost dirty”  

 

TrueAlarm magnet test indication appears as distinct 
“test abnormal” message on display when in test mode 

 

TrueAlarm sensor peak value performance report 

 

“Install Mode” 

allows grouping of multiple troubles 

for uninstalled modules and devices into a single 
trouble condition (typical with future phased 
expansion); with future equipment and devices 
grouped into a single trouble, operators can more 
clearly identify events from the commissioned and 
occupied areas 

 

Module level ground fault searching assists 
installation and service by locating and isolating 
modules with grounded wiring 

 

“Recurring Trouble Filtering”

 allows the panel to 

recognize, process, and log recurring intermittent 
troubles (such as external wiring ground faults), but 
only sends a single outbound system trouble to avoid 
nuisance communications 

 

WALKTEST silent or audible system test performs an 
automatic self-resetting test cycle

 

S4010-0011-5  11/2015

4" x 5" 

Block A

4" x 5" 

Block B

4" x 5" 

Block D

Enhanced System 

Supply

3 available 4" x 5" 

block spaces for 

additional option cards

TrueInsight Remote 
Gateway mounts on 
the back of the 4010ES 
User Interface Panel

 

Mounting Locations for Optional Modules, One-Bay Cabinet

 

Summary of Contents for 4010-9601

Page 1: ...either Class B or Class A operation 48 LED panel mount annunciation provides 40 Red and 8 Yellow pluggable LEDs select models meets ULC requirements optional LED kits are available to change individual LED color to Green or Blue to meet specific site requirements Optional ESS mounted modules door mounted modules and other options include City Connect with or without disconnect switches Alarm Relay...

Page 2: ...of the 4010ES ESS There are 3 available 4 x 5 blocks for mounting 4010ES hardware options Other 4010ES Options The 4010ES City Connect module or the optional Alarm Relay module mount directly to the ESS These options are mutually exclusive Network Media modules mount directly to the 4010ES Network Interface Card The TrueInsight Remote Gateway mounts on the back side of the 4010ES User Interface Pa...

Page 3: ... point category and point selection alphabet characters are not used at this time ADDITIONAL FUNCTION KEYS Event Time Request More Information Request Lamp Test Elevator Bypass City Disconnect Ground Fault Waterflow West Waterflow East Custom label insert LCD NAVIGATION CONTROL Menu selection Vertical and Horizontal position selection buttons 2 X 40 LCD READOUT LCD is backlighted during normal con...

Page 4: ...details TrueAlarm heat sensors can be selected for fixed temperature detection with or without rate of rise detection Utility temperature sensing is also available typically to provide freeze warnings or alert to HVAC system problems Readings can selected as either Fahrenheit or Celsius TrueSense Early Fire Detection Multi sensor 4098 9754 provides photoelectric and heat sensor data using a single...

Page 5: ...by appliances on the notification appliance circuit NAC making it much more difficult and costly to locate and correct the source of a problem Using the TrueAlert magnet test allows each appliance to individually identify its candela setting and address and to briefly operate if desired and using the TrueAlert ES Appliance Self Test feature provides detailed performance verification per appliance ...

Page 6: ...epending on model see model selection below for additional details on specific models Cabinet and door 6 A Enhanced System Supply details Two 3 A Class B IDNAC SLCs for up to 254 addressable notification appliances Class A operation is available using the 4010 9930 Dual Class A IDNAC Isolator DCAI module Up to 2 A of auxiliary power 110 Ah UL 50 Ah ULC battery charger 33 Ah maximum in the control ...

Page 7: ...from the list below 2 Vertical Blocks NA NA 4010 9922 Modular Network Interface Card requires two media modules see below 2 Vertical Blocks 30 mA 30 mA 4010 9818 Network Media Card Wired N A mounts to 4010 9922 55 mA 55 mA 4010 9819 Network Media Card Fiber Optic 25 mA 25 mA 4010 9914 Building Network Interface Card 2 Vertical Blocks 236 mA 236 mA 4010 9923 SafeLINC Internet Interface 2 Vertical B...

Page 8: ...representative for more details LED Kits LEDs are pluggable use to change color for local application requirements Model Description 4100 9843 8 Yellow LED Kit 4100 9844 8 Green LED Kit 4100 9845 8 Red LED Kit 4100 9855 8 Blue LED Kit End User Programming Tools Model Description 4100 8802 End User Programming Unit Software 4100 0292 Custom Label Editing USB Dongle 4100 0295 Port Vectoring Setup an...

Page 9: ...iator English 1 4606 9102CF 4010ES RUI LCD Annunciator French 1 for Canada 4602 9101 Status Command Unit SCU LED Annunciator 1 4602 9102 Remote Command Unit RCU LED Annunciator w control 1 4602 9150 Graphic I O RCU SCU Assembly for custom annunciator panels 1 4602 7101 Graphic I O RCU SCU Assembly for custom annunciator panels 1 4602 7001 RCU for cabinet mount 1 4602 6001 SCU for cabinet mount 1 4...

Page 10: ...ence Installation Instructions 579 1150 Operating Instructions 579 969 Subject Data Sheet Subject Data Sheet 4010ES Agent Release Applications and Accessories S4010 0005 Network Communications S4100 0056 Agent Release Accessories S2080 0010 Multi Signal Fiber Optics S4100 0049 Building Network Interface S4100 0061 4602 Series SCU RCU S4602 0001 SafeLINC Internet Interface S4100 0062 PC Annunciator...