background image

Features 

 

Basic system includes: 

 

Capacity for up to 250 addressable IDNet points, up to 
127 VESDA Air Aspiration Systems interface points, 
and up to 254 addressable notification appliances with 
up to 2000 points of Annunciation; and up to 20 
internal and external card addresses 

 

Color-coded operator interface with membrane keypad 

includes 2 x 40 Super-twist LCD display, 3 programmable 

control keys and 6 programmable LEDs 

 

CPU assembly includes dedicated compact flash memory 

for on-site system information storage and convenient 

Ethernet service port access 

Includes an Enhanced System Supply (ESS) that 

provides power and battery charging (6 A output):  

 

Dual 3 A on-board 

IDNAC

 SLCs (signaling line circuit)  

 

IDNAC SLC provides a 

constant

 29 VDC source voltage 

during alarm, even during battery operation, allowing 

strobes to operate at higher voltage with lower current and 

ensuring a consistent current draw and voltage drop 

margin under primary and secondary power 

 

Efficiencies include lower strobe currents, wiring 

distances up to 2 to 3 times farther than with conventional 

notification, support for more appliances per IDNAC 

SLC, ability to use smaller gauge wiring 

 

IDNAC SLCs are compatible with both TrueAlert ES 
and TrueAlert addressable notification appliances, and 
remote 4009 IDNAC Repeaters to extend power and 
wiring distance even farther and extends supervisory 
capacity by up to 139 additional unit loads or 3 A 

 

Addressable point control is provided by on-board

 IDNet 

2 dual loop SLCs 

that provide

 

two electrically isolated 

channels that support TrueAlarm analog sensors and 

IDNet communications monitoring and control points 

with an 

electrically

 

isolated output channel

 allowing use 

with either shielded or unshielded, twisted or untwisted 

single pair wiring; 

and providing dual short circuit 

isolating output loops

 

 

Battery charger for up to 110 Ah batteries (UL) or up to 

50 Ah batteries (ULC) (33 Ah max in control panel 

cabinet) 

 

2 A programmable function auxiliary output 

 

Remote annunciator module support via RUI (Remote 

Unit Interface) communications port, supports either Class 

B or Class A operation 

 

48 LED panel mount annunciation provides 40 Red and 8 

Yellow pluggable LEDs (select models, meets ULC 

requirements), optional LED kits are available to change 

individual LED color to Green or Blue to meet specific 

site requirements 

Optional ESS mounted modules, door mounted 

modules, and other options include: 

 

City Connect (with or without disconnect switches) 

 

Alarm Relay Module 

 

TrueInsight Remote Gateway 

 

Battery brackets for seismic area protection (see page 2) 

 

 

1-Bay Cabinet 

 

1-Bay Cabinet with 

LED Annunciation 

 

4010ES Panel Type Reference 

Optional block space modules include: 

 

Fire Alarm Physical Bridge and Network Interface Cards 

for Peer-to-Peer fire alarm network communications, 

supports either Class B or Class X operation 

 

Building Network Interface Module (BNIC), SafeLINC 

Internet Interface, and BACpac Ethernet Portal 

 

Dual Class A IDNAC Isolator (DCAI) 

 

Dual RS-232 Module (for printer, PC annunciator or third 

party interface) 

 

VESDA Air Aspiration High Level Interface 

 

Serial DACT  

 

8 Zone IDC Modules Class A or B 

 

4 Point Auxiliary Relay Module 

 
Compatible with Simplex

®

 remotely located: 

 

4098-9757 QuickConnect2 and legacy 4098-9710 
QuickConnect TrueAlarm smoke sensors 

 

4003EC Small Voice Panels 

 

4081 Series, 110 Ah Battery Chargers 

 

4100-7400 Series Graphic Annunciators 

 

4190 Series PC Annunciator, 4190 Series Fiber 
Modems and Physical Bridges  

 

4606-9102 Remote LCD Annunciator, 4100-9400 
Series Remote InfoAlarm Command Centers, and 4602 
Series Status Command Units (SCU) and Remote 
Command Units (RCU) Annunciators 

 

IP communicator compatibility  

 
 
 
 
 
 
 
 
 

 

*   See page 6 for additional listing information. This product has been approved by the 

California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health 

and Safety Code. See CSFM Listing 7165-0026:0369 for allowable values and/or 

conditions concerning material presented in this document. NYC Fire Dept COA #6193.  

Additional listings may be applicable; contact your local Simplex product supplier for the 

latest status. Listings and approvals under Simplex Time Recorder Co. are the property of 

Tyco Fire Protection Products. 

 

 

S4010-0011-5  11/2015

 

 

 

Fire Control Panels 

UL, ULC, CSFM Listed;

 

 Addressable Fire Detection and Control

 

FM, NYC Fire Dept Approved*

 

Basic Panel Modules and Accessories 

 

Summary of Contents for 4010-9601

Page 1: ...either Class B or Class A operation 48 LED panel mount annunciation provides 40 Red and 8 Yellow pluggable LEDs select models meets ULC requirements optional LED kits are available to change individual LED color to Green or Blue to meet specific site requirements Optional ESS mounted modules door mounted modules and other options include City Connect with or without disconnect switches Alarm Relay...

Page 2: ...of the 4010ES ESS There are 3 available 4 x 5 blocks for mounting 4010ES hardware options Other 4010ES Options The 4010ES City Connect module or the optional Alarm Relay module mount directly to the ESS These options are mutually exclusive Network Media modules mount directly to the 4010ES Network Interface Card The TrueInsight Remote Gateway mounts on the back side of the 4010ES User Interface Pa...

Page 3: ... point category and point selection alphabet characters are not used at this time ADDITIONAL FUNCTION KEYS Event Time Request More Information Request Lamp Test Elevator Bypass City Disconnect Ground Fault Waterflow West Waterflow East Custom label insert LCD NAVIGATION CONTROL Menu selection Vertical and Horizontal position selection buttons 2 X 40 LCD READOUT LCD is backlighted during normal con...

Page 4: ...details TrueAlarm heat sensors can be selected for fixed temperature detection with or without rate of rise detection Utility temperature sensing is also available typically to provide freeze warnings or alert to HVAC system problems Readings can selected as either Fahrenheit or Celsius TrueSense Early Fire Detection Multi sensor 4098 9754 provides photoelectric and heat sensor data using a single...

Page 5: ...by appliances on the notification appliance circuit NAC making it much more difficult and costly to locate and correct the source of a problem Using the TrueAlert magnet test allows each appliance to individually identify its candela setting and address and to briefly operate if desired and using the TrueAlert ES Appliance Self Test feature provides detailed performance verification per appliance ...

Page 6: ...epending on model see model selection below for additional details on specific models Cabinet and door 6 A Enhanced System Supply details Two 3 A Class B IDNAC SLCs for up to 254 addressable notification appliances Class A operation is available using the 4010 9930 Dual Class A IDNAC Isolator DCAI module Up to 2 A of auxiliary power 110 Ah UL 50 Ah ULC battery charger 33 Ah maximum in the control ...

Page 7: ...from the list below 2 Vertical Blocks NA NA 4010 9922 Modular Network Interface Card requires two media modules see below 2 Vertical Blocks 30 mA 30 mA 4010 9818 Network Media Card Wired N A mounts to 4010 9922 55 mA 55 mA 4010 9819 Network Media Card Fiber Optic 25 mA 25 mA 4010 9914 Building Network Interface Card 2 Vertical Blocks 236 mA 236 mA 4010 9923 SafeLINC Internet Interface 2 Vertical B...

Page 8: ...representative for more details LED Kits LEDs are pluggable use to change color for local application requirements Model Description 4100 9843 8 Yellow LED Kit 4100 9844 8 Green LED Kit 4100 9845 8 Red LED Kit 4100 9855 8 Blue LED Kit End User Programming Tools Model Description 4100 8802 End User Programming Unit Software 4100 0292 Custom Label Editing USB Dongle 4100 0295 Port Vectoring Setup an...

Page 9: ...iator English 1 4606 9102CF 4010ES RUI LCD Annunciator French 1 for Canada 4602 9101 Status Command Unit SCU LED Annunciator 1 4602 9102 Remote Command Unit RCU LED Annunciator w control 1 4602 9150 Graphic I O RCU SCU Assembly for custom annunciator panels 1 4602 7101 Graphic I O RCU SCU Assembly for custom annunciator panels 1 4602 7001 RCU for cabinet mount 1 4602 6001 SCU for cabinet mount 1 4...

Page 10: ...ence Installation Instructions 579 1150 Operating Instructions 579 969 Subject Data Sheet Subject Data Sheet 4010ES Agent Release Applications and Accessories S4010 0005 Network Communications S4100 0056 Agent Release Accessories S2080 0010 Multi Signal Fiber Optics S4100 0049 Building Network Interface S4100 0061 4602 Series SCU RCU S4602 0001 SafeLINC Internet Interface S4100 0062 PC Annunciator...

Reviews: