Connection Ventilation group module,
type ES-MR-100
Actuator output, 24 Volt DC, max. 12 A
per ES-MR-100 Short time operation. Please don’t forget to install the fuses!
Triggered or not installed fuses are indicated as failure!
Only delayed-action fuses may be applied.
Attention !!
O
S
V=
0,5
24
V (Mains)
6
21,5 V - 26 V (Accu)
S
S
G
O
O
6
7
The terminal for the vent switch supplies a plus potential at “T” when wind/rain detector and SHEV have not been
triggered and if there has been no mains failure. Switching the potential at “Z” or “A” causes a “close” or “open” function
of the connected actuators. If both terminals were connected with “T” the actuators would stop and all position indications
would go out!
A
T
Z
Terminal for vent switch
The enclosed diodeblock must be installed at the last connection point as shown in
the connection diagram. If there is a failure at the line, in the main station will appear
a failure indication!
If the diode block is installed in the control panel there
will be no failure indication but the actuator lines will not be monitored!
Attention!!
S
O
G
µA=
M
24V
40 - 100µA
= Connection for monitoring loop -
actuator line
6
7
Notice:
Do not connect contact “F” of the
actuator with “G” in the control panel. This
would cause a short circuit at the actuator
lines.
Connection for actuators
Fuses
Fuse actuator: 5 or 10 A delayed-action (at vent group module)
Only use delayed-action fuses.
Attention!!
Triggering resp. a lack of this fuse is indicated as a failure
(at the specific modules of the electrical control panel and in the main station.)
Installation manual ESM-T/X-EV (24 A / 48 A / 72 A)
Page 17/20
SIMON RWA SYSTEME GmbH, Passau
ESM-T/X-EV with power supply
Dublications, also in extracts, are only legal with express authorisation from SIMON RWA SYSTEME GmbH Passau
®
Polarity changes between “S” and “O” in case of open or close. At switching
position “OPEN” “S” has plus and “O” has minus potential. At “G” the monitoring
loop is connected. If the actuator lines are without failure you can measure a
closed current in the
line “G”
of
40 - 100µA