![SIMON RWA ESM-T/X-EV Installation Manual Download Page 14](http://html1.mh-extra.com/html/simon-rwa/esm-t-x-ev/esm-t-x-ev_installation-manual_1275743014.webp)
red LED “RWA” = RWA (=SHEV triggered)
green LED “FTZ” = failure free button loop
green LED “RM” = failure free
smoke detector loop
green LED “BMZ” = failure free contact loop
green LED “OK” = this SHEV system and all ventilatilation
groups are ready for use (collective
failure indication)
yellow LED “OPEN” = open command to all vent groups
yellow LED “CLOSE” = close command to all vent groups
2
3
DIP- switches
3
4
5
Terminal ribbon cable
Terminal ribbon cable
WRES
RES
SHEV
CLOSE
OPEN
BMZ
RM
FTZ
ON
OFF
Adjustment by the customer “ON”. May only be changed at VdS-systems and
only after consultation with the manufactor.
The DIP switches are factory-adjusted in a way so that a failure in the
monitoring loops causes an automatic triggering of the SHEV alarm. If
the operator wants to cause simply a failure indication instead of an auto-
matic triggering he has to throw the DIP switches of the particular
loops leftwards.
Central relay module, type ES-ZL-100
* 270 k
12/04)
(until manufacture year
Installation manual ESM-T/X-EV (24 A / 48 A / 72 A)
Page 13/20
SIMON RWA SYSTEME GmbH, Passau
ESM-T/X-EV with power supply
For each SHEV group an ES-ZL-100 module is
required. This module controls all commands
relevant for SHEVs like “OPEN” via the break glass
button or the automatic triggers like smoke detector
and also the dry opener contact of the BMZ. These
lines are connected via a 27 k * resistor and closed
current monitored. In case of short circuit or
interruption the SHEV groups get triggered
automatically
Adjustment by the customer “ON”. May only be changed at VdS-systems and
only after consultation with the manufactor.
Adjustment by the customer “ON”. May only be changed at VdS-systems and
only after consultation with the manufactor.
Adjustment by the customer “ON”. May only be changed at VdS-systems and
only after consultation with the manufactor.
Attention!
The
adjustment
s
b
y
the
customer
may
only
be
changed
by
authorized
qualified
personell.
False
adjustment
s
o
f
the
DIP
switches
can
lead
to
a
malfunction
of
the
SHEV
system!
Dublications, also in extracts, are only legal with express authorisation from SIMON RWA SYSTEME GmbH Passau
®