Ventilation group module, type ES-MR-100
LZ
LA
Z PAR
A PAR
Z TOT
A TOT
END
DIP-switches (adjustment samples)
ON
OFF
Central vent command in closing direction is active for this vent group.
Parallel connection of this vent group module in closing direction to the
foregoing vent group
Dead man operation for vent function in “close” switched off.
Switch not used
Closes the monitoring loop and consequently the collective failure indication
of the SHEV group (must be in “EIN” position at the last vent module). All
groups between must be switched off.
For each ventilation group a ES-MR-100 module is
necessary. This module supplies the connected actuators
with voltage in pole changing technique. The max. output
current is 12 A per module.
1
6
7
6
green LED “OK” = ready for use
yellow LED “OPEN” = actuators open
yellow LED “CLOSE” = actuators close
(LED “OPEN/CLOSE” at the same time =
actuators stopped, e.g. by vent switch)
Connection ribbon cable
Connection ribbon cable
5A
10A
Installation manual ESM-T/X-EV (24 A / 48 A / 72 A)
Page 16/20
SIMON RWA SYSTEME GmbH, Passau
ESM-T/X-EV with power supply
Dublications, also in extracts, are only legal with express authorisation from SIMON RWA SYSTEME GmbH Passau
®
The actuator line is monitored for interruption by an end of
the line diode unit. The maximum cable cross section is
2,5 mm² when connected directly at the terminals. For
bigger cross sections a block terminal can be installed.
The output is fused by a delay micro fuse with 5 A resp.
10 A.
Central vent command in opening direction is active for this vent group.
Parallel connection of this vent group module in opening direction to the
foregoing vent group
Dead man operation for vent function in “open” switched off.