User manual for - FLOW METER SPP-N118
Register Write
Range
Register description
4Bh
Yes
0 ÷ 2
“SourCE”
parameter in
“rELAy2”
menu (kind of value controlled
relay):
0
- “FLo”;
1
- “bAt”;
2
- “tot”;
4Ch
Yes
0 ÷ 3
“t PrEc”
parameter in
“rELAy2”
menu (precision of thresholds and
hysteresis while relay is controlled due to total flow counter value):
0
- “ 0”;
1
- “ 0.0”;
2
- “ 0.00”;
3
- “0.000”
4Dh
Yes
0 ÷ 1
“t unit”
parameter in
“rELAy2”
menu (the unit of thresholds and
hysteresis while relay is controlled due to total flow counter value):
0
- lit.;
1
- m
3
;
70h
6
Yes
-999 ÷ 1999 The value of „
X
” coordinate of point
no. 1
of the user defined
characteristic, expressed in 0,1%
71h
6
Yes
0 ÷ 9999
The value of „
Y
” coordinate of point
no. 1
of the user defined
characteristic, no decimal point included
72h
6
÷ 95h
6
Further pairs of „
X
” - „
Y
” coordinates of points
no. 2
÷
19
of the user
defined characteristic
96h
6
Yes
-999 ÷ 1999 The value of „
X
” coordinate of point
no. 20
of the user defined
characteristic, expressed in 0,1%
97h
6
Yes
0 ÷ 9999
The value of „
Y
” coordinate of point
no. 20
of the user defined
characteristic, no decimal point included
C0h
Yes
0 ÷ 1
“
modE
” parameter in “
HOLd
” menu (type of detected changes):
0
- peaks;
1
- drops
C1h
Yes
0 ÷ 9999
“
PEA
” parameter in “
HOLd
” menu (minimum detectable change, no
decimal point included)
C2h
Yes
0 ÷ 199
“
timE
” parameter in “
HOLd
” menu,
maximum peaks' (or drops')
display time expressed in seconds
C3h
Yes
0 ÷ 1
“
HdiS
” parameter in “
HOLd
” menu (the type of values displayed on
the display
):
0
- current measurement value;
1
- peaks (or drops) values
C4h
Yes
0 ÷ 1
“
H r1
” parameter in “
HOLd
” menu (the control mode of relay R1 and
LED R1)
:
0
- control depends on current measurement values;
1
- control depends on peaks (or drops) values;
C5h
Yes
0 ÷ 1
“
H r2
” parameter in “
HOLd
” menu (the control mode of relay R2 and
LED R2) :
0
- control depends on current measurement values;
1
- control depends on peaks (or drops) values;
D0h
Yes
0 ÷ 1
“b unit”
parameter in
“bAtCH”
menu (the unit of volume while
batcher counter result displaying):
0
- lit.;
1
- m
3
;
D1h
Yes
0 ÷ 3
“b PrEc”
parameter in
“bAtCH”
(precision of batcher counter result
displaying):
0
- “ 0”;
1
- “ 0.0”;
2
- “ 0.00”;
3
- “0.000”
51