User manual - FLOW METER SPI-638
Register Write
Range
Register description
Yes
0 ÷ 5
“
OUtmod
” parameter in “
OUtPUt
” menu (active voltege output
mode)
0
- voltage
output disabled
;
1
- voltage
output enabled
with
0
÷5V
mode;
2
- voltage
output enabled with
1÷5V
mode
;
3
- voltage
output enabled with
0÷10V
mode
;
4
- voltage
output enabled with
2÷10V
mode
;
5
- voltage
output controlled via RS-485 interface
A1h
2
A2h
2
Yes
0 ÷ 999999
“
OUt LO
” parameter in “
OUtPUt
” menu,
no decimal point included
A3h
2
A4h
2
Yes
0 ÷ 999999
“
OUt HI
” parameter in “
OUtPUt
” menu,
no decimal point included
A5h
2
Yes
0 ÷ 999
“
Lo r
” parameter in “
OUtPUt
” menu, for active current output and
active voltage output, expressed in 0.1%
Yes
0 ÷ 299
“
Lo r
” parameter in “
OUtPUt
” menu for passive current output,
expressed in 0.1%
A6h
2
Yes
0 ÷ 199
“
Hi r
” parameter in “
OUtPUt
” menu for active and passive current
output, expressed in 0.1%
Yes
0 ÷ 99
“
Hi r
” parameter in “
OUtPUt
” menu for active voltage output,
expressed in 0.1%
A7h
2
Yes
0 ÷ 3
“
AL
” parameter in “
OUtPUt
” menu (active current output value on
critical exception):
0
- no change;
1
- 22.1 mA;
2
- 3.4 mA;
3
- 0 mA
Yes
0 ÷ 2
“
AL
” parameter in “
OUtPUt
” menu (passive current output value on
critical exception):
0
- no change;
1
- 22.1 mA;
2
- 3.4 mA
Yes
0 ÷ 5
“
AL
” parameter in “
OUtPUt
” menu (active voltage output value on
critical exception):
0
- no change;
1
- 11 V;
2
- 5.5;
3
- 1.2 V;
4
- 0.6 V;
5
- 0 V
A8h
2
Yes
0 ÷ 2
“SourCE”
parameter in
“OUtPUt”
menu (kind of value controlled
active current output):
0
- “FLo”;
1
- “bAt”;
2
- “tot”;
A9h
2
Yes
0 ÷ 3
“t PrEc”
parameter in
“OUtPUt”
menu (precision of “
OUt LO
”
and “
OUt HI
” parameters displaying, while active current output is
controlled due to total flow counter value):
0
- “ 0”;
1
- “ 0.0”;
2
- “
0.00”;
3
- “0.000”
AAh
2
Yes
0 ÷ 1
“t unit”
parameter in
“OUtPUt”
menu (the unit of “
OUt LO
” and
“
OUt HI
” parameters displaying, while active current output is
controlled due to total flow counter value):
0
- unit;
1
- 1000un;
ABh
2
Yes
0 ÷ 3
“b PrEc”
parameter in
“OUtPUt”
menu (precision of “
OUt LO
”
and “
OUt HI
” parameters displaying, while active current output is
controlled due to batcher counter value):
0
- “ 0”;
1
- “ 0.0”;
2
- “
0.00”;
3
- “0.000”
ACh
2
Yes
0 ÷ 1
“b unit”
parameter in
“OUtPUt”
menu (the unit of “
OUt LO
” and
“
OUt HI
” parameters displaying, while active current output is
controlled due to batcher counter value):
0
- unit;
1
- 1000un;
D0h
Yes
0 ÷ 1
“b unit”
parameter in
“bAtCH”
menu (the unit of volume while
batcher counter result displaying):
0
- unit;
1
- 1000un;
56