28
m
CAUTION
The boiler should be located observing the required
clearances, and provide safe, adequate service ac-
cess.
6.9
Plumbing connections
The plumbing connections have the following characteristics
and dimensions.
135
101
65 65 65 65
=
=
48
420
M
Sc
Sc
U
G
E
R
Fig. 21
Description
MIA-30
M - System flow
Ø 22 mm
R - System return
Ø 22 mm
U - Domestic hot water output
Ø 15 mm
E - Domestic hot water inlet
Ø 15 mm
G - Gas cock connection
Ø 15 mm
Sc - Condensate outlet
Ø 21.5 mm
m
CAUTION
A sealed system must only be filled by a competent
person (see section Method of filling a sealed sys-
6.9.1 Plumbing accessories (optional)
To facilitate plumbing and gas connections to the systems, the
accessories as shown in the table below are available and are
to be ordered separately from the boiler.
DESCRIPTION
CODE
Installation plate
8075448
NOTE:
kit instructions are supplied with the accessory itself or
are to be found on the packaging.
6.10 Condensate outlet/collection
To ensure safe disposal of the condensate produced by the
flue gases, reference should be made to BS6798:2009.
The boiler incorporates a condensate trap which has a seal of
75 mm, therefore no additional trap is required.
The condensate trap can be filled prior to the installation of
the flue by carefully pouring 1 litre of water into the exhaust
connection.
NOTE: All pipework must have a continuous fall from the boil-
er and must be resistant to corrosion by condensate, copper
or steel is NOT suitable. It should be noted that the connec-
tion of a condensate pipe to a drain may be subject to local
building control requirements (Dealing with Condensate - see
Appendix 1).
6.11 Gas supply
MIA-30
boilers leave the factory prearranged for gas G20 and
can also work with G31 without the need for any type of me-
chanical conversion. Simply select parameter
"03"
(see “Pa-
rameter setting and display") page 37 and set the type of gas
to be used.
If changing the type of gas to be used, carry out the entire
appliance
"COMMISSIONING"
The gas connection must be made using seamless steel or
copper tube.
Where the piping has to pass through walls, a suitable insulat-
ing sleeve must be provided.
When sizing gas piping, from the meter to the boiler, take into
account both the volume flow rates (consumption) in m3/h
and the relative density of the gas in question.
The sections of the piping making up the system must be such
as to guarantee a supply of gas sufficient to cover the maxi-
mum output available from the boiler, limiting pressure loss
between the gas meter and any apparatus being used to not
greater than 1.0 mbar for family II gases (natural gas).
An adhesive data badge is sited inside the front panel; it con-
tains all the technical data identifying the boiler and the type
of gas for which the boiler is arranged.
a
WARNING
Once installation has been completed, check that
the joints are air tight as indicated in the installation
Standards.
m
CAUTION
It is recommended that the gas line has a suitable
filter.
m
CAUTION
If the gas supply is changed from G20 to G31, mark
the box on the TECHNICAL DATA PLATE.
X
G31 - 37 mbar
Summary of Contents for MIA-30
Page 3: ...3...
Page 8: ...8...
Page 14: ...14...
Page 23: ...23...
Page 48: ...48 9 EXPLODED VIEWS Frame...
Page 49: ...49 Hydraulic assembly...
Page 50: ...50 Exchanger Combustion...
Page 51: ...51 Control panel...
Page 52: ...52 Additional components...
Page 53: ...53...