6
Model
I-HE 35 MF & E-HE 35 MF
Heat output - Gas pressures available
Nominal (80-60°C)
kW
34.1
Nominal (50-30°C)
kW
37.2
Reduced (80-60°C)
kW
8.8
Reduced (50-30°C)
kW
9.6
Heat input
Nominal
MJ/h
125.6
Reduced Nat/LPG 1
MJ/h
32.5
Losses after shutdown to 50°C (EN 483)
W/h
95
Supply voltage
V-Hz
240 /50
Adsorbed power consumption
W
145
C.H. setting range
°C
20/80
Water content boiler
l
6.1
Maximum water head
bar
3
Maximum temperature
°C
85
Capacity of the heating expansion vessel
l
10
Pressure of the heating expansion vessel
bar
1
Exhaust fumes temperature at max flow rate (80-60°C)
°C
70
Exhaust fumes temperature at min. flow rate (80-60°C)
°C
65
Exhaust fumes temperature at max flow rate (50-30°C)
°C
40
Exhaust fumes temperature at min. flow rate (50-30°C)
°C
35
Smokes flow min/max
kg/h
14/60
CO
2
at max/min flow rate G20 Natural gas
%
9.0/9.0
CO
2
at max/min flow rate G31 LP gas
%
10.0/10.0
Weight when empty
kg
68
Main burner nozzle
Quantity nozzles
n°
1
G20/G31 Nat Gas / LP gas injector diameter
ø
8.5 / 5.2
1.3
TECHNICAL FEATURES
Page 15 of 40
Summary of Contents for Green Planet I-HE 35 MF