64
EN
CAUTION
– The height of the boiler is to be such that disassem-
bly and maintenance interventions are facilitated.
2.9
Plumbing connections
The plumbing connections have the following characteristics and
dimensions.
175
48
65 65 65 65
=
=
48
400
M
Sc
Sc
U
G
E
R
Fig. 12
Description
Brava Slim HE
25
30
35
40
M - System delivery
Ø 3/4" G
R - System return
Ø 3/4" G
U - Domestic hot water output
Ø 1/2" G
E - Domestic hot water inlet
Ø 1/2" G
G - Gas supply
Ø 3/4" G
Sc - Condensate outlet
Ø 20 mm
2.9.1
Plumbing accessories (optional)
To facilitate plumbing and gas connections to the systems, the
accessories as shown in the table below are available and are to
be ordered separately from the boiler.
DESCRIPTION
CODE
Installation plate
8075441
Curve kit
8075418
Cocks kit
8091806
Wall mount replacement kit for other makers
8093900
Fitting protection Kit
8094530
Polyphosphate dosing kit
8101700
Dosing recharge kit
8101710
Solar kit for instant combination boilers
8105101
NB:
kit instructions are supplied with the accessory itself or are
to be found on the packaging.
2.10
Condensate outlet/collection
In order to collect the condensate, it is recommended that:
– the appliance condensate outlets and the smoke outlet are
ducted
– a neutralising device is prearranged
– the outlet incline is
>3%
.
CAUTION
– The condensate outlet duct must be airtight, suitably
sized to that of the siphon and must not be restricted
at any point.
– The condensate outlet must be constructed in full
compliance of the National or Local regulations in
force.
– Before commissioning the appliance, fill the siphon
with water.
2.11
Gas supply
Brava Slim HE
boilers leave the factory prearranged for gas G20
(methane) and can also work with G31 (propane) without the need
for any type of mechanical conversion. Simply select parame-
ter
”03”
(see “
Parameter setting and display
") and set the type
of gas to be used.
Boiler connection to the gas mains must be carried out in full
compliance with installation Standards in force.
Before connecting the boiler to the gas mains, the user must en-
sure that:
– the type of gas is correct for the appliance
– the pipes are clean
– the gas supply pipe is the same dimension as or greater than
that of the boiler fitting (G3/4") and with a load loss less than
or equal to that contemplated between the gas mains and the
boiler.
DANGER
Once installation has been completed, check that the
joints are air tight as indicated in the installation Stand-
ards.
CAUTION
It is recommended that the gas line has a suitable filter.