EN
3.3
Parameter setting and display
To go into the parameter menu:
– from the selected mode (eg. WINTER)
– press the buttons
r
and
t
(for approximately 5 seconds) at
the same time until
“PAR 01”
(parameter number) and the val-
ue set (0-4) appears on the display
– press the button
t
to scroll up the list of parameters and then
r
to scroll down the list
NB:
holding the buttons
r
or
t
increases the speed of the
scrolling movement.
– once the required parameter has been reached, press the but-
tons
>
or
<
to modify the value within the permitted range. The
modifications are stored automatically.
When all the parameter modifications have been made, exit the
parameter menu by pressing and holding down the buttons
r
and
t
at the same time
until the initial screen is displayed.
3.4
List of parameters
Type
No.
Description
Range
Unit of
measure-
ment
Step
Default
CONFIGURATION
PAR
01
Index showing boiler power in kW
1 = 25; 2 = 30; 3 = 35; 4 = 40
0 .. 3
-
1
1-2-3-4
PAR
02
Hydraulic configuration
0 = rapid
1 = hot water tank with thermostat
2 = hot water tank with sensor
3 = two programmer
0 .. 3
-
1
0
PAR
03
Gas Type Configuration
0 = G20; 1 = G31
0 .. 1
-
1
0
PAR
04
Combustion configuration
0 = sealed chamber with combustion control
1 = open chamber with smoke probe
0 .. 1
-
1
0
PAR
07
Ignition power
0 .. 40
-
1
0
PAR
08
External sensor value correction
-5 .. +5
°C
1
0