Load loss accessory Ø 80 mm
Description
Code
Load loss (mm H
2
O)
Edea 30
Inlet
Outlet
90° curve MF
8077450
0,25
0,30
45° curve MF
8077451
0,20
0,20
Horizontal extension W. 1000
mm
8077351
0,20
0,20
Vertical extension W. 1000
mm
8077351
0,20
0,20
Wall terminal
8089501
0,10
0,35
Roof outlet terminal (*)
8091204
1,10
0,15
Duct kit C(10)3
6296550
-
-
6296543
-
1,8
Description
Code
Load loss (mm H
2
O)
Edea 40
Inlet
Outlet
90° curve MF
8077450
0,30
0,4
45° curve MF
8077451
0,25
0,25
Horizontal extension W. 1000
mm
8077351
0,25
0,25
Vertical extension W. 1000
mm
8077351
0,25
0,25
Wall terminal
8089501
0,15
0,50
Roof outlet terminal (*)
8091204
1,5
0,2
Duct kit C(10)3
6296543
-
2,8
(*) The losses of the roof outlet terminal at inlet include the
manifold code 8091400.
NOTE:
for the boiler to operate correctly it is necessary that a
minimum distance of 0.50 m of the duct is respected with a
90° inlet curve.
6.12.6 Separate ducts (Ø 50 mm)
The
Edea
boiler is configured for use in Ø 50 mm discharge
flues. To ensure correct boiler operation, parameter PAR31
(long flues) should be set on the basis of the length of the in-
stalled flues, as indicated in the table.
PAR 31
Edea 30
Ø 50 mm outlet
Discharge diaphragm
0
1 x 90° elbow + 2 metres
leave it mounted
0
1 x 90° elbow + 6 metres
remove
2
1 x 90° elbow + 10 metres
remove
4
1 x 90° elbow + 14 metres
remove
6
1 x 90° elbow + 18 metres
remove
8
1 x 90° elbow + 22 metres
remove
10
-
-
12
-
-
PAR 31
Edea 40
Ø 50 mm outlet
Discharge diaphragm
0
1 x 90° elbow + 12 metres
remove
2
-
-
4
-
-
6
-
-
8
-
-
NOTE:
to remove the discharge diaphragm, proceed as illus-
trated in “Fig. 26”.
120
Ø 80
170
170
Ø 80
320
400
125
125
Fig. 28
Example: calculation of the load loss of a
Edea 30
boiler.
Accessories Ø 80 mm
Code
Quantity
Load loss (mm H
2
O)
Inlet Outlet Total
Extension W. 1000 mm
(horizontal)
8077351
9
9 x
0,20
-
1,80
Extension W. 1000 mm
(horizontal)
8077351
9
-
9 x
0,20
1,80
90° curve
8077450
2
2 x
0,25
-
0,50
90° curve
8077450
2
-
2 x
0,30
0,60
Wall terminal
8089501
1
0,10
-
0,10
Wall terminal
8089501
1
-
0,35
0,35
TOTAL
5,15
(installation permitted since the total of the load loss of the
accessories used is less than 15 mmH
2
O).
Summary of Contents for 8116902
Page 4: ...4 ...
Page 14: ...14 ...
Page 52: ...52 9 EXPLODED VIEWS Frame ...
Page 53: ...53 Hydraulic assembly ...
Page 54: ...54 Exchanger Combustion ...
Page 55: ...55 Control panel ...
Page 56: ...56 Gas valve Oversleeve Fan ...
Page 77: ...77 ...
Page 78: ...78 ...
Page 79: ...79 ...