79
EN
– press the button
o
to confirm (approximately 3 seconds) and
access the default value which is flashing
– press the button
>
and select "1" (LPG)
– press the button
o
for at least 3 seconds to confirm the mod-
ification. the value will stop flashing.
Procedure which MUST be carried out after:
–
the nozzles for gas conversion
–
changing the gas valve following a fault
–
changing the the electronic board following a fault
–
electrode
–
fan
–
burner
– go into the parameter section (if not already there) by press-
ing the buttons
<
and
o
(approximately 5 seconds) at the
same time until
"tS"
(installer) appears on the 2 digits of the
display which alternate with
"0.1"
(parameter number) and a
"2"
(set value)
– keep the button
>
pressed and scroll through the parameters
until reaching parameter "tS 4.9"
– press the button
o
to confirm (approximately 3 seconds) and
access the default value which is flashing
– press the button
>
or
<
to set the value
at "49"
– press the button
o
to confirm the modification The value will
stop flashing
– keep the button
>
pressed and scroll through the parameters
until reaching parameter "tS 7.0"
– press the button
o
to confirm (approximately 3 seconds) and
access the default value which is flashing
– press the button
>
or
<
to set the value
"5"
– press the button
o
to confirm the modification The value will
stop flashing
– exit the parameter section by pressing and holding down the
buttons
<
and
o
at the same time
(approximately 5 seconds)
until the delivery temperature is displayed.
m
IMPORTANT
To complete this task the user
MUST
carry out the fol-
lowing procedure.