MSA510/1
List of commands / service mode English
MSA510/1 · Date
04.05.2016 · Art.
No.
83520 · Mod.
status
38/16
36
Position value (-120.00 ... 5000.00 mm)
In order to avoid leaps occurring around the maximum value at the 0 posi-
tion, this maximum value is limited to 5000 mm. This enables recording of
a range of up to -120 mm in negative travel direction.
0
0
-1 +1
-1
+1
-12000
+499999 -12000
+499999
Variable boundary
If there is the requirement of extending the measurement range in neg-
ative direction, a positive value can be programmed as the boundary via
service mode interface.
e. g.: boundary = 2000 mm
0
0
-1 +1
-1
+1
-
312000
+200000
-312000
6 List of commands / service mode
Parameters: 4800 (default) ... 115200 baud, no parity, 8 bit, 1 start bit, 1
stop bit, no handshake
Data code: ASCII (if not otherwise specified)
Value range: 2/3 Byte: 0 ... 65535 / 0 ... 2
23
The service mode serves for test purposes, automatic configuration, and
for computer coupling. Via the RS232 serial interface, the MSA510/1 can
be operated directly from a computer or terminal. The interface must have
the following settings:
4800 baud, no parity, 8 bit word length, 1 start bit, 1 stop bit, no hand-
shake.
Generally, the PC (or the terminal) sends an uppercase letter, together
with additional parameters, if required. The MSA510/1 sends a reply with a
concluding <CR>.
Command
Length Reply
Description
a0
2/8
"MSA510/1>" Device type/software identifier
a1
2/7
"V0.03>"
Software version
b
1/8
"012345"
non-offset tape value
cxy
3/5
"3f0b"
Read out EEPROM values Hex-ASCII; xy 00
... 63 dec