MSA510/1
Commissioning English
MSA510/1 · Date
04.05.2016 · Art.
No.
83520 · Mod.
status
38/16
30
•
EX: 8-pole plug pin (M12 A coded)
For mating connector and cable extension accessories see chapter
Signal SSI (acc. to RS422) Signal RS485 Pin
Zeroing/Configuration
Calibration
1
+UB
+UB
2
Data+
DÜA
3
Data-
DÜB
4
GND
GND
5
Cycle+
nc
6
Cycle-
nc
7
nc
nc
8
•
E8: 9-pole D-SUB plug pin
Signal SSI (acc. to RS422) Signal RS485 Pin
+UB
+UB
1
Cycle+
nc
2
Data+
DÜA
3
Zeroing/Configuration
Configuration 4
GND
GND
5
nc
nc
6
Cycle-
nc
7
Data-
DÜB
8
nc
nc
9
5 Commissioning
The input (Zeroing/Configuration) should never be operated open to avoid
potential interferences.
After mounting tape and sensor and after complete wiring, the system is
ready for use. Alignment of sensor and tape was carried out by the manu-
facturer.
The configuration process is dependent on the output circuit:
MSA510/1 with RS485 output circuit (and with optional SIKONETZ3-
protocol)
The Zeroing/Configuration input is used to distinguish between "Service
Mode" and "SIKONETZ3" protocol. The distinction occurs only when the
operating voltage is switched on and is controlled via the assignment of the
"Zeroing/Configuration" input at the time when the unit is switched on:
viewing side =
plug-in side
plug pin
viewing side =
plug-in side
plug pin
NOTICE