AG02
Installation English
AG02 · Date
31.10.2012 · Art.
No.
82270 · Mod.
status
354/12
40
Danger of fire
Fuse protection is required as a protection against damage caused by
defective devices.
`
Electronic automatic fuses of the E-T-A company or load circle monito-
ring devices of the Murr Elektronik company are suitable solutions for
this purpose.
`
For the nominal currents refer to the technical data in chapter
.
Electromagnetic compatibility (EMC)
The following measures are required in order to ensure the actuator's elec-
tromagnetic compatibility:
`
All lines for connecting the actuator must be shielded.
`
The cable shield must be applied to both sides.
`
The retractable ferrite (supplied with the AG02) is to be attached to
the supply line near the 3-pole connector (only with Position transdu-
cer: ABM).
`
The drive is to earthed via the flat connection with a strand section of
at least 4 mm² (only with Position transducer: ABM).
Basically, all connections are protected against external interference.
Choose a place of operation that excludes inductive or capacitive interfe-
rence influences on the actuator. When mounting the system keep a maxi-
mum possible distance from lines loaded with interference. If necessary,
provide additional installations including screening shields or metallized
housings.
Admissible power input
Supply for the actuator shall be sized sufficiently. When accelerating,
power input may be higher than nominal current for a short period. The
voltage values are a function of the device design and can be referred to in
the technical data in chapter
.
`
Therefore, the strand cross section for actuator supply must be min.
0,5 mm
2
.
WARNING
CAUTION
NOTICE
NOTICE