25
INSTALLATION
ENGLISH
Connecting Electricity
Electrical Requirements
This appliance must be installed and grounded on a
branch circuit by a qualified technician in accordance
with the National Electrical Code ANSI/NFPA NO. 70
- latest edition.
All wiring should conform to local and NEC codes.
This range requires a single-phase, 3 wire, A.C
120/208 V or 120/240 V 60 Hz electrical system. Use
only a 3-conductor or a 4-conductor UL - listed range
cord with closed-loop terminals, open-end spade
lugs with upturned ends or similar termination. Do not
install the power cord without a strain relief.
A range cord rated at 40 amps with 120/208 or
120/240 minimum volt range is required. If a 50 amp
range cord is used, it should be marked for use with
1
3
/
8
" diameter connection openings. This appliance
may be connected by means of a conduit or power
cord. If a conduit is being used, go to page 27 for
3 wire conduit connections
or
4 wire conduit
connections
.
WARNING
%
Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack
in the line so that the range can be moved if
servicing is ever necessary.
%
The power supply cord and plug should not
be modified. If the plug will not fit the outlet,
have a proper outlet Installed by a qualified
electrician.
%
Using an extension cord to connect the
power is prohibited. Connect the power cord
and plug directly.
%
Electrical ground is required on this
appliance.
%
Make sure that the power cord is not pinched
by the range or heavy objects.
Failure to
do so can result in serious burns or electrical
shock.
%
Do not use a damaged power plug, power
cord, or loose power outlet.
%
Do not put a fuse in a neutral or ground
circuit.
%
Do not connect the ground wire to plastic
plumbing lines, gas lines, or hot water pipes.
Specified power-supply-cord kit rating
Range rating, watts
Specified
rating of
power
supply-
cord kit,
amperes
Diameter
(inches) of range
connection
opening
120/240
volts
3-wire
120/208
volts
3-wire
Power
cord
Conduit
8,750 -
16,500
16,501 -
22,500
7,801 -
12,500
12,501 -
18,500
40 or 50A
50
1
3
/
8
"
1
3
/
4
"
1
1
/
8
"
1
3
/
8
"
3, 4 - Wire Electrical Wall Receptacle
4 Wire receptacle (14-50R)
3 Wire receptacle (10-50R)