Connector Layout
The connections of the +24 V supply (X4: pin 1 and pin 2) or the GND sup-
ply (X4: pin 3 and pin 4) are internally bridged. To supply the module, only
one connection to a +24 V pin (pin 1 or pin 2) and a GND pin (pin 3 or pin
4) is required. The bridged connections may be used for further looping of
the +24 V supply and the GND supply. However, it must be ensured that
through looping, a total current of 6 A per connection is not exceeded!