instabus EIB
Technical Product Information
April 2006
Touch panel UP 588
5WG1 588-2AB01
Touch panel UP 588/11
5WG1 588-2AB11
Touch panel UP 588/21
5WG1 588-2AB21
Accessories: Design frame, anodised aluminium
5WG1 588-8AB01
Technical Manual
UP 588, 6 pages
Siemens AG
Automation and Drives Group
Update: http://www.siemens.de/gamma
©
Siemens AG 2006
Electrical Installation Technology
Subject to change without prior notice
P.O.Box 10 09 53, D-93009 Regensburg
2.3.1.4/2
Technical Specifications
Power supply
•
Bus voltage: via the bus line
•
External power supply
•
Touch-Panel UP 588 and Touch-Panel UP 588/11
230 V AC ±10%, 50/60 Hz
•
Touch-Panel UP 588/21
12 - 36V DC, 120mA
10 - 28V AC, 50/60 Hz, 120mA
Operating elements
•
Learning button for toggling between
normal/addressing mode
•
Resistive matrix with 6 x 10 fields
(touch-sensitive display)
Display elements
•
Red programming LED for displaying
normal/addressing mode
•
320 x 240 pixel display with graphic capability and
backlighting
Connections
•
Bus line: EIB bus terminal, screwless
0.6 ... 0.8mm
∅
solid
insulation strip length 5mm
•
Power supply
Insulation strip length: 6...7mm
The following conductors/conductor cross-sections
are permitted:
-
0.5...2.5mm
2
solid
-
0.5...1.5mm
2
finely-stranded
Mechanical data
•
Housing: plastic
•
Dimensions (WxHxD): 190 x 156 x 58mm
•
Mounting depth in flush-type box: 52mm
•
Installation: screwed into the relevant flush-type box
•
Dimensions of relevant flush-type box (WxHxD):
164 x 138 x 65 mm, included with supply
•
Weight: approx. 350 g
Electrical safety
•
Degree of pollution
2
•
Type of protection (according to EN 60529):
IP 20
•
Overvoltage
category:
III
•
Bus: safety extra-low voltage SELV DC 24 V
•
Device complies with EN50090-2-2
EMC requirements
Complies with EN 61000-6-1 and EN 61000-6-2
Ambient conditions
•
Climatic withstand capability: EN 50090-2-2
•
Ambient operating conditions: 0°C to +45°C
•
Storage temperature: -25°C to +70°C
•
Relative humidity (not condensing): 5 % to 93 %
Markings
KNX/EIB
CE mark
In accordance with the EMC guideline (residential and
functional buildings) and the low voltage guideline