Siemens UP 588 Product Information Download Page 3

 

instabus EIB

 

Technical Product Information 

April 2006  

Touch panel UP 588 

5WG1 588-2AB01  

Touch panel UP 588/11 

5WG1 588-2AB11 

Touch panel UP 588/21 

5WG1 588-2AB21 

Accessories: Design frame, anodised aluminium 

5WG1 588-8AB01 

Siemens AG 

UP 588, 6 pages 

Technical Manual 

Automation and Drives Group 

 

 

Electrical Installation Technology 

©

 Siemens AG 2006 

Update: http://www.siemens.de/gamma 

P.O.Box 10 09 53, D-93009 Regensburg 

Subject to change without prior notice 

 

 

2.3.1.4/3 

Location and function of the conjunction-  

and operating elements  

 
The device connections as well as the learning button 
and programming LED which are required for the com-
missioning stage are accessible at the back of the de-
vice. Diagram 1 shows the back of the device. 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 

 

Diagram 2: Location of the display and  

operating elements 

 
 

A1 

Terminal compartment for the connection of the 
power supply terminal  

A2 

Programming LED 

A3 

Learning button 

A4 

Bus terminal 

A5 

Latching 

 
The connection of the bus cable is carried out via a 
standard bus terminal which is inserted in the corre-
sponding terminal locator on the right-hand side of the 
housing. The learning button and the programming LED 
are located on the left next to the module slot for the 
bus terminal. The terminal for the power supply is on 
the left-hand side of the device. The terminal must be 
withdrawn in order to connect the power supply cables. 
 
 
 
 
 
 
 

A6

 

 
A6 

for adjusting the contrast 

 
The contrast of the display can be changed via potenti-
ometer. The contrast is optimally pre-set for operation 
in most environments at the factory. Changes should be 
made only for extreme conditions. 
 
 

Mounting and wiring 

 
General description 
The device may only be installed in the flush-type box 
that is supplied. For the cable entry into the flush-type 
box, the bus cable must be inserted into the bottom left 
opening (B3) and the power supply cable must be in-
serted into the opening on the right-hand side (B2). The 
bus and power supply cable may not be fed through an 
opening together into the flush-type box. Within the 
box, the cable should be led so that a minimum distance 
of 10mm is guaranteed between the bus and the power 
supply cable. 
 
 

B1

B2

B3

B4

 

B6

 

B7

B5

 

 

 

Diagram 3: Installation of the touch panel 

A1

 

A2

A3 

A4

 

 

LED Prog.

 

 

 

       

 

N L 

 

 

 

 

A5

 

Summary of Contents for UP 588

Page 1: ...an alarm page with 4 alarm signals and 2 text messages as well as the execution of time controlled tasks The following accessories are required for the touch panel Design frame aluminium 5WG1 588 8AB01 Application Programs 01 07 Touch Panel vision 802103 display and operation of up to 70 EIB standard functions on 7 display pages display of an alarm page with 4 alarm signals and 2 text messages exe...

Page 2: ...l display with graphic capability and backlighting Connections Bus line EIB bus terminal screwless 0 6 0 8mm solid insulation strip length 5mm Power supply Insulation strip length 6 7mm The following conductors conductor cross sections are permitted 0 5 2 5mm2 solid 0 5 1 5mm2 finely stranded Mechanical data Housing plastic Dimensions WxHxD 190 x 156 x 58mm Mounting depth in flush type box 52mm In...

Page 3: ...is inserted in the corre sponding terminal locator on the right hand side of the housing The learning button and the programming LED are located on the left next to the module slot for the bus terminal The terminal for the power supply is on the left hand side of the device The terminal must be withdrawn in order to connect the power supply cables A6 A6 for adjusting the contrast The contrast of t...

Page 4: ... the bus terminal and the power supply terminal to the cables the terminals are inserted in the corresponding openings on the touch panel Once the bus voltage has been applied the learning button can be pressed and the physical device address can be pro grammed The LED should be extinguished when the physical address has been programmed The device is then screwed into the box using the four screws...

Page 5: ... and C3 3 each with four terminal contacts Care should be taken not to damage the two test sockets C3 1 either by accidentally connecting them to the bus conductor or with the screwdriver when trying to remove the bus terminal Carefully insert the screwdriver in the wire entry slot of the grey section of the bus terminal C3 3 and pull the bus terminal C3 out of the built in device When the red sec...

Page 6: ...anel UP 588 21 5WG1 588 2AB21 Accessories Design frame anodised aluminium 5WG1 588 8AB01 Technical Manual UP 588 6 pages Siemens AG Automation and Drives Group Update http www siemens de gamma Siemens AG 2006 Electrical Installation Technology Subject to change without prior notice P O Box 10 09 53 D 93009 Regensburg 2 3 1 4 6 Notes ...