background image

Application Manual

Nr. 02

Hotel rooms – room automation

Synco™

& Gamma

18

Variants

Key

Product no. and description

Stock number

5a

AP 118 automation module box

5WG1 118-4AB01

6a

UP 525/13 universal dimmer, 1 x 250 W

5WG1 525-2AB13

7a

UP 520/13 blind actuator, 1 x 6 A

5WG1 520-2AB13

8a

UP 510/13 binary output , 2 x 10 A

5WG1 510-2AB13

Room HVAC control

4-pipe fan coil unit

·

 

Heating and cooling with hot or chilled water

·

 

Modulating control of heating and cooling valve

·

 

Automatic or manual fan control

XFNC04 B21 HQ

The temperature in every room is acquired and controlled. Every room sends its heat/cooling energy request to the
heating/refrigeration plant. These plants are controlled depending on the outside temperature and the heat/cooling
energy requests received from the rooms. During nonoccupancy times (rooms not booked), the room temperatures
are automatically lowered via the integrated hotel booking system. Open windows are always automatically detected
and the temperatures of such rooms are lowered/raised to save heating/cooling energy. The room temperatures are
also lowered/raised during the day, if the guest is not present.

Lighting control

Presence detectors (hotel card switches) help save energy by automatically switching the lighting and individual
electric circuits off when guests are not present.

Blinds control

When a room is not booked (or, if desired, when the guest is absent), a weather station outside the building protects
up to 4 façades from extreme sunlight in the summer. This function helps to keep the rooms cool. The weather
station also protects the blinds from damage caused by strong winds or other natural influences. On sunny winter
days, the weather station raises the blinds to let solar radiation make a natural heat contribution.
When the guest is present, the blinds can be controlled via the pushbuttons and automatic operation is off.

Remote control

Integration of a webserver facilitates remote control and monitoring on a PC or smartphone via webbrowser.

Summary of Contents for Synco-Gamma

Page 1: ...www siemens com bt integrated applications Synco Gamma Application Guide Hotel buildings ...

Page 2: ......

Page 3: ...and primary plant With all applica tions the focus is placed on energy efficiency and comfort The different variants offer room automation with fan coil units radiators and floor heating systems as well as ventilation and VAV plant with a host of products from Siemens KNX range From simple solutions with fan coil units including switching of electric circuits to VAV sys tems for larger rooms with ...

Page 4: ...erial 2 Fan coil unit radiator lighting sun protection hotel room Efficiency class B 16 Heating and cooling 2 control loops Automatic or manual fan control 1 or 3 speed Automatic or manual changeover of heat ing cooling mode Window contact central detection of open windows Detection of presence via hotel card switch Presence and time dependent control of HVAC lighting sun protection and power supp...

Page 5: ...matic detection of occupancy ensures enhanced comfort Time and daylight dependent shading control saves heat ing cooling energy when the room is not occupied Display of energy efficiency saves energy Facility manager and personnel are informed about energy waste and error messages e g open windows during nonoccupancy times 4 Fan coil unit radiator lighting sun protection hotel room Efficiency clas...

Page 6: ...ntact central detection of open windows Detection of presence via hotel card switch Presence and time dependent control of HVAC lighting sun protection and power sup ply to the room Central operation and display of HVAC lighting and sun protection Pushbuttons for SOS Make up room and Do not disturb Time and presence dependent individual room temperature con trol saves up to 20 heating energy Separ...

Page 7: ... are sent to the facility manager and to personnel 9 VAV plant indoor air quality control lighting and sun protection restaurant area Efficiency class A 47 Heating and cooling indoor air quality control Fully integrated VAV application with temperature CO2 and volumetric air flow control Automatic data exchange between room HVAC and primary plant VAV controllers for optimization of ventilation sys...

Page 8: ...esence and brightness dependent control of lighting saves up to 45 light energy Monitoring of operating times and error messages from the lighting system ensure reliability Time and daylight dependent shading control saves up to 30 heating cooling energy Display of energy efficiency saves energy Fault status messages are sent to the facility manager and to personnel 11 Primary plant Efficiency cla...

Page 9: ...eeds But when auto matically switching to another operating mode the setpoints are reset to those of the room group Lighting A typical lighting scenario could look as follows When the hotel card is inserted the basic lighting is switched on Then other lights can be switched on manually via the pushbuttons When leaving the room all lights are automatical ly turned off after a certain period of time...

Page 10: ... the management station and logged on the UP 588 touch panel as a trend When using Synco 700 devices RMB795B RMS705B opening the door can either be counted or logged as an event In each case 4 channels available Hotel booking system Integration in hotel booking system Integration of an OPC server with suitable commercially available software facilitates the connection from the KNX bus to the Micro...

Page 11: ...roduction of heat and cooling energy thanks to automatic data exchange with primary plant Room setup 1 Room thermostat RDF600KN The RDF600KN acquires the room temperature and controls the fan coil unit and the radiator in the bathroom accordingly The room operating mode can be selected and the temperature setpoints can be adjusted on the room thermostat 2 STA23 electrothermal actuator The STA23 ad...

Page 12: ...1 room control box 5WG1 641 3AB01 4 RS 525 23 universal dimmer 1 x 250 W 5WG1 525 2AB23 5 RL 521 23 blind actuator 1 x 6 A 5WG1 521 4AB23 6 RS 510 23 binary output 2 x 10 A 5WG1 510 2AB23 7 RXZ97 1 gateway EnOcean KNX S55842 Z101 8 EnOcean window contact 3rd party product 9 EnOcean hotel card switch 3rd party product 10 AP 221 wall transmitter EnOcean 1 fold neutral 5WG4 221 3AB10 11 Rocker neutra...

Page 13: ...s are always automatically detected and the temperatures of such rooms are lowered raised to save heating cooling energy The room temperatures are also slightly lowered raised during the day if the guest is not present Lighting control Presence detectors hotel card switches help save energy by automatically switching lighting off when the room is not occupied Blinds control When a room is not book...

Page 14: ...o the Economy level Presence dependent lighting control When the room is no longer occupied lighting is automatically switched off Blinds control The weather station AP257 32 with its built in GPS receiver measures solar radiation and controls shad ing to protect the façade against sunlight Up to 4 façades can be selected for automatic and individual control In cold winter nights the blinds are lo...

Page 15: ...on Sheet Individual Rooms TAAC01 DG1 HQ 2 pipe fan coil unit with radiator RDG100KN Synco Application Sheet Centrally Managed Rooms QCA001 MB7 HQ Central control of room temperature control equipment RMB795B Synco Application Sheet Central Operating and Monitor ing OWAL03 772 HQ Local plant operation and monitoring via local network with webbrowser OZW772 Gamm Application Sheet Light ing L00001 N5...

Page 16: ...and Do not disturb Demand compensated production of heat and cooling energy thanks to automatic data exchange with primary plant Room setup 1 QAX98 4 solar room unit The QAX98 4 acquires the room temperature The 2 knobs are used to adjust the room temperature setpoint and to select the operating mode present absent 2 RXB21 1 room controller The RXB21 1 controls the room temperature via the fan coi...

Page 17: ...to control the blinds 15 DELTA pushbutton The DELTA pushbutton activates signal lamp DND Do not disturb outside and inside the room In the bathroom it switches the lighting Device list Key Product no and description Stock number 1 QAX98 4 solar room unit S55623 H107 2 RXB21 1 room controller BPZ RXB211 FC 10 3 AQR2570 room sensor basic module S55720 S203 206 AQR2532 room sensor temperature S55720 ...

Page 18: ... booking system Open windows are always automatically detected and the temperatures of such rooms are lowered raised to save heating cooling energy The room temperatures are also lowered raised during the day if the guest is not present Lighting control Presence detectors hotel card switches help save energy by automatically switching the lighting and individual electric circuits off when guests a...

Page 19: ...s raised to the Comfort level Then it is lowered again to the Precomfort level Presence dependent lighting control When the room is no longer occupied the lighting and individual electric circuits are automatically switched off Blinds control The weather station AP257 32 with its built in GPS receiver measures solar radiation and controls shad ing to protect the façade against sunlight Up to 4 faç...

Page 20: ...plication Sheet Individual Rooms XFNC04 B21 HQ 4 pipe fan coil unit RXB21 1 Synco Application Sheet Centrally Managed Rooms QCA001 MB7 HQ Central control of room temperature control equipment RMB795B Synco Application Sheet Central Operating and Monitor ing OWAL03 772 HQ Local plant operation and monitoring via local network with webbrowser OZW772 Gamma Application Sheet Lighting L00001 N5 HQ Cent...

Page 21: ... automatic data exchange with primary plant Room setup 1 UP 204 Contouch room controller The UP 204 acquires the room temperature and sends temperature setpoint shift operating mode and fan speed commands to the RXB room controller via the KNX bus The Contouch room controller can also be used to control the lighting and the blinds 2 RXB21 1 room controller The RXB21 1 controls the room temperature...

Page 22: ...ELTA pushbutton 2 fold with labeling field MUR DND One of the pushbuttons can be used to activate signal lamp DND Do not disturb outside and inside the room The other pushbutton is used to activate the MUR function Make up room This signal is sent to the KNX bus via pushbutton interface UP 220 Device list Key Product no and description Stock number 1 UP 204 Contouch room controller 5WG1 204 2AB11 ...

Page 23: ...20 2AB13 UP 221 2 pushbutton 1 fold neutral 5WG1 221 2DB12 12a 13a DELTA hotel card switch with insert 5TG4 820 UP 220 21 I O pushbutton interface 2 inputs outputs 5WG1 220 2AB21 Room HVAC control XFNC04 B21 HQ 4 pipe fan coil unit Heating and cooling with hot and chilled water Modulating control of heating and cooling valve Automatic or manual fan control The temperature in every room is acquired...

Page 24: ...nce dependent heating control When the presence detector signals room occupancy the room temperature is raised or lowered to the Comfort level When the guest leaves the room by opening the door the door contact as the last device sends a signal causing the room temperature to be lowered or raised to the Precomfort level Presence dependent lighting control When the room is no longer occupied the li...

Page 25: ...ion Sheet Individual Rooms XFNC04 B21 HQ 4 pipe fan coil unit RXB21 1 Synco Application Sheet Centrally Managed Rooms QCA001 MB7 HQ Central control of room temperature control equipment RMB795B Synco Application Sheet Central Operating and Monitor ing OWAL03 772 HQ Local plant operation and monitoring via local network with webbrowser OZW772 Gamma Application Sheet Lighting L00002 N5 HQ Daylight a...

Page 26: ...and compensated production of heat and cooling energy thanks to automatic data exchange with primary plant Room setup 1 RDG100KN room thermostat The RDG100KN acquires the room temperature and controls the fan coil unit and the radiator in the bathroom accordingly The room operating mode can be selected and the temperature setpoints can be adjusted on the room thermostat 2 STA23 electrothermal actu...

Page 27: ...tton is used to acti vate the MUR function Make up room Device list Key Product no and description Stock number 1 RDG100KN room thermostat S55770 T163 2 STA23 electrothermal actuator S55174 A101 3 DELTA hotel card switch with insert 5TG4 820 4 N 528 31 universal dimmer main module 1 x 300 W 5WG1 528 1AB31 5 N 502 02 combi switching actuator 8 x 16 A 8 inputs 5WG1 502 1AB02 6 N 523 02 blind actuato...

Page 28: ... heat cooling energy requests received from the rooms During nonoccupancy times rooms not booked the room temperatures are automatically lowered via the integrated hotel booking system Open windows are always automatically detected and the temperatures of such rooms are lowered raised to save heating cooling energy The room temperatures are also slightly lowered raised during the day if the guest ...

Page 29: ...losses Presence dependent lighting control When the room is no longer occupied the lighting is automatically switched off after a delay time Blinds control The weather station AP257 32 with its built in GPS receiver measures solar radiation and controls shad ing to protect the façade against sunlight Up to 4 façades can be selected for automatic and individual control In cold winter nights the bli...

Page 30: ...on Sheet Individual Rooms TAAC01 DG1 HQ 2 pipe fan coil unit with radiator RDG100KN Synco Application Sheet Centrally Managed Rooms QCA001 MB7 HQ Central control of room temperature control equipment RMB795B Synco Application Sheet Central Operating and Monitor ing OWAL03 772 HQ Local plant operation and monitoring via local network with webbrowser OZW772 Gamma Application Sheet Lighting L00001 N5...

Page 31: ...th primary plant Room setup 1 RDF600KN room thermostat The RDF600KN acquires the room temperature and controls the fan coil unit and the radiator in the bathroom accordingly The room operating mode can be selected and the temperature setpoints can be adjusted on the room thermostat 2 STA23 electrothermal actuator The STA23 adjusts the valve according to the positioning signal it receives from the ...

Page 32: ...F600KN room thermostat S55770 T293 2 STA23 electrothermal actuator S55174 A101 3 RMS705B switching and monitoring device 6 x 4 A 8 inputs S55370 C100 105 4 S 290 door window contact 5WG1 290 7AB11 5 Rocker neutral 5TG6 201 Insert universal switch 5TA2 156 6 Rocker with Bell symbol SOS 5TG6 207 Insert universal switch 5TA2 156 7 Rocker double with labeling field MUR DND 5TG6 212 Insert pushbutton 2...

Page 33: ...ontrolled depending on the outside temperature and the heat cooling energy requests received from the rooms During nonoccupancy times rooms not booked the room temperatures are automatically lowered via the integrated hotel booking system Open windows are always automatically detected and the temperatures of such rooms are lowered raised to save heating cooling energy The room temperatures are als...

Page 34: ...e dependent lighting control When leaving the room the electric circuits are inter rupted causing the lighting to be switched off after a delay time When the hotel card is reinserted the electric circuits are closed again Remote control and monitoring Using a webbrowser all rooms can be controlled and monitored via webserver OZW The following pa rameters can be monitored Current state of windows a...

Page 35: ...via the KNX bus The UP 227 can also be used to control the lighting and the blinds 2 AQR2532 room sensor with AQR2570 basic module The AQR acquires and controls the room temperature in the bathroom via the radiator 3 AP 562 02 valve actuator The AP 562 02 drives the radiator valve It receives the positioning signal from the UP 227 or the AQR controller 4 AP 118 automation module box The AP 118 has...

Page 36: ...AB02 4 AP 118 automation module box 5WG1 118 4AB01 5 RS 525 23 universal dimmer 1 x 250 W 5WG1 525 2AB23 6 RL 521 23 blind actuator 1 x 6 A 5WG1 521 4AB23 7 RS 510 23 binary output 2 x 10 A 5WG1 510 2AB23 8 S 290 door window contact 5WG1 290 7AB11 UP 220 21 I O pushbutton interface 2 inputs outputs 5WG1 220 2AB21 9 Rocker neutral 5TG6 201 Insert universal switch 5TA2 156 UP 220 21 I O pushbutton i...

Page 37: ...ntrol Presence detectors hotel card switches help save energy by automatically switching the lighting off when the room is not occupied Blinds control When a room is not booked or if desired when the guest is absent a weather station outside the building protects up to 4 façades from extreme sunlight in the summer This function helps to keep the rooms cool The weather station also protects the bli...

Page 38: ...ndent lighting control When the room is no longer occupied the lighting is automatically switched off after a delay time Blinds control The weather station AP257 32 with its built in GPS receiver measures solar radiation and controls shad ing to protect the façade against sunlight Up to 4 façades can be selected for automatic and individual control In cold winter nights the blinds are lowered to i...

Page 39: ...perating mode to the N 605 via the KNX bus The QMX3 P37 can also be used to control the lighting and the blinds 2 QMX3 P70 room operator unit The QMX3 P70 acquires the room temperature and sends the temperature value the setpoint shift and the operating mode to the N 605 via the KNX bus 3 N 605 thermal drive actuator The N 605 features 6 inputs to connect pushbuttons and 6 outputs to control elect...

Page 40: ... Key Product no and description Stock number 1 QMX3 P37 room operator unit display and operation temperature S55624 H108 2 QMX3 P70 room operator unit temperature humidity CO2 S55624 H104 3 N 605 thermal drive actuator 5WG1 605 1AB01 4 AP 641 room control box 5WG1 641 3AB01 5 RS 525 23 universal dimmer 1 x 250 W 5WG1 525 2AB23 6 RL 521 23 blind actuator 1 x 6 A 5WG1 521 4AB23 7 RS 510 23 binary ou...

Page 41: ...ver measures solar radiation and controls shading to protect the façade against sunlight Up to 4 façades can be selected for automatic and individual control In cold winter nights the blinds are lowered to improve the building s thermal insulation On sunny winter days the blinds are raised allowing sunlight to enter the room so that energy is gained When the room is occupied automatic operation is...

Page 42: ...lighting control When the room is no longer occupied the lighting is automatically switched off after a delay time Blinds control The weather station AP257 32 with its built in GPS receiver measures solar radiation and controls shad ing to protect the façade against sunlight Up to 4 façades can be selected for automatic and individual control In cold winter nights the blinds are lowered to im prov...

Page 43: ...oom setup 1 AQR2532 room sensor with AQR2576 basic module The AQR sends information about the room temperature and the indoor air quality to the ventilation controller which controls the temperature and the proportion of fresh air in the supply air 2 N 141 02 KNX DALI gateway The N141 transmits the KNX signal to the DALI bus to switch and dim the lighting In the other direction status information ...

Page 44: ... minimum and maximum limitation of supply air temperature Control of supply air temperature via the heat recovery system the air heating coil valve and the air cooling coil valve in sequence Frost protection with frost protection sensor on the air side and controller internal 2 phase frost protection function Monitoring of supply and extract air fans with differential pressure switches Monitoring ...

Page 45: ...pushbutton In this case lighting control is stopped and the brightness level in the room is maintained as long as presence is detected Presence dependent lighting control The presence detector UP258E21 allows up to 4 lighting groups to be switched and controlled and detects presence within its range If persons are detected lighting is switched on at the required brightness level When persons leave...

Page 46: ...ion Product no Synco Application Sheet Central Operating and Monitor ing AECE01 U2B HQ Room supply air temperature cascade control with plate heat recovery system recirculated air damper air heat ing coil and air cooling coil RMU720B Synco Application Sheet Central Operating and Monitor ing OWAL03 772 HQ Local plant operation and monitoring via local network with webbrowser OZW772 Gamma Applicatio...

Page 47: ...3 of the floor heating system 2 QMX3 P70 room operator unit The QMX3 P70 acquires the indoor air quality and sends its value to the ventilation controller which adjusts the amount of fresh air required 3 GDB181 1E KN VAV compact controller The GDB controls the VAV dampers The setpoints of the volumetric air flow are shifted depending on the amount of air demanded by the room thermostat 4 N 141 02 ...

Page 48: ...ol 5WG1 258 2EB21 7 UP 223 2 pushbutton triple neutral 5WG1 223 2DB12 UP 117 12 bus coupling unit BTM 5WG1 117 2AB12 8 UP 588 color touch panel 5WG1 588 2AB13 Optional Key Product no and description Stock number 9 N 125 12 power supply 5WG1 125 1AB12 10 N 151 IP viewer 5WG1 151 1AB01 11 OZW772 x webserver OZW772 x 12 RMB795B central control unit S55370 C162 C167 13 AP 257 22 weather station 5WG1 2...

Page 49: ...mount of air demanded by the VAV controller The heating plant is controlled depending on the heat request from the ventilation controller and the room thermostats plus the outside temperature The refrigeration plant is controlled depending on the cooling ener gy request from the ventilation controller Nonoccupancy times are detected by presence detectors and can be set for the night and every room...

Page 50: ...on also protects the blinds from damage caused by strong winds or other natural influences and controls them at dusk and according to temperatures to save heating energy during winter nights Finally sun tracking control and shadow outline tracking allow a maximum of natural light to enter the rooms offering optimum working conditions Remote control Integration of a webserver facilitates remote con...

Page 51: ...e configuration of constant light control with only one presence detector Manual switching and dimming is made possible via the pushbutton In this case lighting control is stopped and the brightness level in the room is maintained as long as presence is detected Presence dependent lighting control The presence detector UP258E21 allows up to 4 lighting groups to be switched and controlled and detec...

Page 52: ...limits were made If nonefficient operating states occur the user is notified via e mail or smartphone app The limit values can be set by the user Secondary documents The Application Sheets listed below describe individual controller applications and contain detailed information They can be downloaded from the Internet at www siemens com hit Application no Name of application Product no Synco Appli...

Page 53: ...STA23 of the floor heating system 2 AQR2532 room sensor with AQR2576 basic module The AQR acquires the indoor air quality and sends its value to the ventilation controller which controls the proportion of fresh air in the supply air 3 GDB181 1E KN VAV compact controller The GDB controls the VAV dampers Its setpoints of the volumetric air flow are shifted depending on the amount of air demanded by ...

Page 54: ...tuator 1 x 6 A 5WG1 521 4AB23 7 RS 510 23 binary output 2 x 10 A 5WG1 510 2AB23 8 UP258E21 presence detector with constant light control 5WG1 258 2EB21 9 Rocker 2 fold neutral 5TG6 205 UP 116 31 DELTA bus coupling unit 2 fold 5WG1 116 2AB31 10 Rocker 2 fold neutral 5TG6 205 Insert pushbutton 2 fold 2 NO contacts 5TD2 111 11 STA23 electrothermal actuator S55174 A101 Optional Key Product no and desc...

Page 55: ... controller The heating plant is controlled depending on the heat request from the ventilation controller and room thermostats plus the outside temperature The refrigeration plant is controlled depending on the cooling ener gy request from the ventilation controller Nonoccupancy times during the night can be set for every room in a time program During these periods of time the room temperatures ar...

Page 56: ...riods the operating mode is set to Economy resulting in a lower temperature setpoint Hence valuable heating energy can be saved during the night and on days of rest After that the setpoint is raised to the Precomfort level Presence dependent heating control When the presence detector signals room occupancy the room temperature is raised to the Comfort level Then it is lowered again to the Precomfo...

Page 57: ... be viewed changed if required The state of lighting on off Room occupancy The state of blinds raised or lowered Display of energy efficiency The OZW772 webserver is able to display the HVAC system s energy efficiency which reminds the user if from the point of view of energy efficiency settings beyond the permitted limits were made If nonefficient operating states occur the user is notified via e...

Page 58: ... controller The RMU720B controls the refrigeration plant depending on the cooling energy request from the ventilation plant and the rooms 3 RMU720B ventilation controller The RMU720B controls the primary ventilation plant depending on the heat cooling energy and proportion of fresh air requests from the rooms Device list Key Product no and description Stock number 1 RMH760B heating controller RMH7...

Page 59: ...ing mode Control of a 1 or 2 stage burner Control of boiler temperature by modulating burner with modulating DC 0 10 V control Demand compensated precontrol for external consumers Demand compensated precontrol Refrigeration control CBA001 U2B HQ Demand dependent chilled water generation On off of plant depending on the request from consum ers request via KNX Plant on via external contact demand Co...

Page 60: ...and the request for volumetric air flow from the VAV controller GDB The pressure setpoints of the ventilation system are shifted depending on the room s demand for supply air Demand compensated production of heat cooling energy Heat RMH or cooling energy RMU is supplied only when requested by the primary ventilation controller RMU or the room thermostats RDG RDF or the room controller RXB demand c...

Page 61: ...ation Air Conditioning ADCE06 U2B HQ Supply air temperature control for VAV systems RMU720B Synco Application Sheet Boiler with boiler pump HB0001 H6B HQ Demand compensated boiler temperature control with controlled maintained boiler return temperature RMH760B Synco Application Sheet Primary controller for external consumers H0F001 H6B HQ Demand compensated precontrol for external consumers Synco ...

Page 62: ......

Page 63: ... challenges Siemens has the answers The information in this document contains general descriptions of technical options available which do not always have to be present in individual cases The required features should therefore be specified in each individual case at the time of closing the contract Siemens Switzerland Ltd 2013 BT_0024_EN Siemens Switzerland Ltd Building Technologies Division Inte...

Reviews: