Application Manual
Nr. 11
Eenergy center – primary control
Synco™
& Gamma
59
Ventilation control
ADCE06 U2B HQ
Supply air temperature control for VAV systems
·
Control of speed-controlled fans with differential pres-
sure control
·
Control of air dampers depending on indoor air quality
·
Control of supply air temperature via the heat recovery
system, the valve of the air cooling coil and the valve of
the air cooling coil in sequence
Heating control
HB0001 H6B HQ
H0F001 H6B HQ
Weather-compensated boiler temperature control with con-
trolled maintained boiler return temperature
·
Weather-compensated boiler temperature control
·
Maintained boiler return temperature with own mixing
valve
·
Control of boiler pump depending on boiler operating
mode
·
Control of a 1- or 2-stage burner
·
Control of boiler temperature by modulating burner with
modulating DC 0…10 V control
Demand-compensated precontrol for external consumers
·
Demand-compensated
precontrol
Refrigeration control
CBA001 U2B HQ
Demand-dependent chilled water generation
·
On/off of plant depending on the request from consum-
ers (request via KNX)
·
Plant on via external contact (demand)
·
Control of chilled water pump, with pump kick and mon-
itoring of volumetric flow
·
Control of recooling pump, with pump kick and monitor-
ing of volumetric flow
·
Control of chilled water flow temperature through acti-
vation of recooling pump and switching on of refrigera-
tion machine
·
Control of recooling temperature via recooling valve
and activation of recooling fans
·
Control of refrigeration machine via on/off command
compressor, refrigeration valve and monitoring input for
fault status signal from the refrigeration machine. The
Summary of Contents for Synco-Gamma