Hardware
Configuration and Assembly
4.4 Connection and Wiring
4.4.1
Connection Areas for SIWAREX MS
All connections can be made from the front.
Figure 4-1
SIWAREX MS connection areas
4.4.2 Shielding
Connection
Special attention must be given to the shield strip for the shielded lines. Only
correct installation guarantees that the system will be immune to interference. A
cable is shielded to decrease the affects of magnetic, electrical and
electromagnetic interference on this line. Interference on cable shielding is routed
to ground through the shielding connection clamp. To ensure that this interference
does not become a source of interference, a low impedance connection to ground
is especially important.
Only use wires with braided shielding (see recommended cable types in chapter
). Shielding should provide at least 80% coverage.
The shielding clamps must be ordered separately. The following image shows the
shield clamp assembly.
4-12 SIWAREX
MS