Configuration
6.2 Configuring the busbar run layout
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
113
Height changes and T units
All changes ≤ 6 m are regarded as changes in height. With larger changes in height, the
guidelines for vertical planning must be taken into account.
Additional fixed points must be configured before or after changes in height and directly
at T units.
L ≤ 6 m
/
①
Fixed point
With a maximum height difference of 6 m, expansion compensation is not necessary.