Configuration
6.1 Basic knowledge for configuring
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
87
Type 2: LX...-AS2
●
All tag distances between the external conductors are identical
●
Distance dimension of PEN(N) variable
●
The PEN(N) tag is arranged between the phases
Phase sequence
+LX-.E
L1
L2
PEN(N)
L3
+LX-.F
L3
PEN(N)
L2
L1
+LX-.G
L3
L2
PEN(N)
L1
+LX-.H
L1
PEN(N)
L2
L3
Tag diLX-P*/N*
●
For P* (external conductor - external conductor) 450 to 750 mm
●
For N* (external conductor L2 - PEN(N)) 150 to 405 mm
Type 3: LX...-AS3
●
All tag distances of the external conductors are identical
●
Distance dimension of PEN(N) variable
●
PEN(N) tag external
Phase sequence
+LX-.A
L1
L2
L3
PEN(N)
+LX-.B
PEN(N)
L3
L2
L1
+LX-.C
L3
L2
L1
PEN(N)
+LX-.D
PEN(N)
L1
L2
L3
Tag diLX-P*/N*
●
For P* (external conductor - external conductor) 450 to 750 mm
●
For N* (external conductor PEN(N)) 150 to 400 mm