Commissioning
SITRANS WF100
28
Operating Instructions, 02/2012, 7ML19985NB01-01
For example:
If the design flowrate is 6 T/H, then:
Test weight 60% = 6 t/h × 60% × 45 g/t/h
= 162 g
Test weight 80% = 6 t/h × 80% × 45 g/t/h
= 216g
Therefore the test weight should be between 162 and 216 g.
If an available test weight of 200 g is used, then:
Test rate = 200 g ÷ 45 g t/h
= 4.444 t/h
Perform the zero calibration as described in the Calibration section of the integrator manual.
After the completion of the zero calibration, a span calibration, as described in the integrator
instruction manual, can be performed with the test weight(s) applied.
Span
1.
Install the calibration pulley to the bracket on the flowmeter housing.
2.
Hang the test weight over the calibration pulley using the test weight cable.
3.
Perform the span calibration as described in the calibration section of the integrator
instruction manual.
Summary of Contents for SITRANS WF100
Page 1: ...SITRANS Solid Flowmeters SITRANS WF100 Operating Instructions 02 2012 ...
Page 6: ...Table of contents SITRANS WF100 4 Operating Instructions 02 2012 7ML19985NB01 01 ...
Page 8: ...Introduction SITRANS WF100 6 Operating Instructions 02 2012 7ML19985NB01 01 ...
Page 26: ...Installing Mounting SITRANS WF100 24 Operating Instructions 02 2012 7ML19985NB01 01 ...
Page 28: ...Connecting SITRANS WF100 26 Operating Instructions 02 2012 7ML19985NB01 01 ...
Page 32: ...Commissioning SITRANS WF100 30 Operating Instructions 02 2012 7ML19985NB01 01 ...
Page 42: ...Technical data SITRANS WF100 40 Operating Instructions 02 2012 7ML19985NB01 01 ...
Page 44: ...Dimension drawings SITRANS WF100 42 Operating Instructions 02 2012 7ML19985NB01 01 ...