Technical data
11.1 Technical data
SITRANS TR200/TR300
72
Operating Instructions, 06/2010, A5E01071992-03
Millivolt transmitter input point
Measured variable
DC voltage
Sensor type
DC voltage source (DC voltage source is possible
via a resistor that is connected externally)
Units of measurement
mV
Measuring cycle
≤ 250 ms for 1 sensor with break monitoring
Break monitoring
Can be switched off
Measuring range
Setting range max. -100 ... 1100 mV
Min. measuring span
2 mV or 20 mV
Overload capacity of the input point
-1.5 ... 3.5 V DC
Input resistance
≥ 1 MΩ
Characteristic curve
Linear to voltage or special characteristic curve
Output
Output signal
4 ... 20 mA, two-wire line
With SITRANS TR300, additionally with
communication according to HART rev. 5.9
Auxiliary power supply
11 ... 35 V DC (to 30 V in Ex "i"/"ic"; to 32 V with
Ex "nA")
Max. load
(U
aux
-11 V)/0.023 A
Overrange
3.6 mA ... 23 mA infinitely adjustable
(default range: 3.80 mA to 20.50 mA)
Error signal (e.g. in case of sensor failure)
3.6 mA ... 23 mA continuously adjustable
(default value: 22.8 mA)
Setting time:
Dead time
< 360 ms
T63 (without electrical attenuation, without
dead time)
< 260 ms
Attenuation
Software filter 1st order 0 ... 30 s (can be set in
the parameters)
Protection
Against reverse polarity
Electrical isolation
Input for output
DC 2.12 kV (AC 1.5 kV)
Summary of Contents for sitrans tr300
Page 7: ...Table of contents SITRANS TR200 TR300 6 Operating Instructions 06 2010 A5E01071992 03 ...
Page 21: ...Installation SITRANS TR200 TR300 20 Operating Instructions 06 2010 A5E01071992 03 ...
Page 69: ...Service and maintenance SITRANS TR200 TR300 68 Operating Instructions 06 2010 A5E01071992 03 ...
Page 81: ...Dimension drawings SITRANS TR200 TR300 80 Operating Instructions 06 2010 A5E01071992 03 ...
Page 93: ...Glossary SITRANS TR200 TR300 92 Operating Instructions 06 2010 A5E01071992 03 ...