Functions
9.9 Calculation of differential value/mean value
SITRANS TR200/TR300
Operating Instructions, 06/2010, A5E01071992-03
47
9.9
Calculation of differential value/mean value
The differential and averaging circuit interfaces have the following special features compared
to the standard connection:
Setting the start of scale value and full scale value:
● Enter the start of scale value and full scale value for both individual sensors first. The
start of scale value and full scale value are the same for both sensors. It is not possible to
assign different measuring ranges for the individual sensors in the parameters. Tip: use
the largest measuring range.
● Following this, assign the parameters for the start of scale value and full scale value for
the differentiation or the average value measurements.
Sensor calibration:
● Trim the individual sensors at the selected limits of the measuring range. The
differentiation or average set in the parameters cannot be trimmed.
9.10
Electrical damping
You can set the filter time constant of electrical damping to a point within a range from 0 to
30 s.
9.11
Current transmitter function (only for SITRANS TR300)
You can use this function to switch the transmitter into constant current mode for test
purposes. In that case, the output current no longer corresponds to the process variable.
Summary of Contents for sitrans tr300
Page 7: ...Table of contents SITRANS TR200 TR300 6 Operating Instructions 06 2010 A5E01071992 03 ...
Page 21: ...Installation SITRANS TR200 TR300 20 Operating Instructions 06 2010 A5E01071992 03 ...
Page 69: ...Service and maintenance SITRANS TR200 TR300 68 Operating Instructions 06 2010 A5E01071992 03 ...
Page 81: ...Dimension drawings SITRANS TR200 TR300 80 Operating Instructions 06 2010 A5E01071992 03 ...
Page 93: ...Glossary SITRANS TR200 TR300 92 Operating Instructions 06 2010 A5E01071992 03 ...