Technical data
11.1 Technical data
SITRANS TR200/TR300
70
Operating Instructions, 06/2010, A5E01071992-03
1)
Prerequisites: same resistance for all three lines.
Resistance-type transmitter input point
Measured variable
Ohmic resistance
Sensor type
Resistance, potentiometer
Units of measurement
Ω
Interface
Standard connection
1 resistance-type transmitter (R) in two-wire,
three-wire or four-wire input
Averaging
2 resistance-type transmitters in two-wire input
for averaging
Differentiation
2 resistance-type transmitters in two-wire input
(R1 - R2 or R2 - R1)
Connection
Two-wire input
Line resistance can be assigned in the
parameters ≤100 Ω (loop resistance)
Three-wire input
No trim necessary
1)
Four-wire input
No trim necessary
Sensor current
≤ 0.45 mA
Measuring cycle
≤ 250 ms for 1 sensor with break monitoring
Break monitoring
Always active (cannot be switched off)
Short circuit monitoring
Can be switched on/off (default value = OFF)
Measuring range
Setting range max. 0 ... 2200 Ω (see table in
chapter Digital measuring error (Page 76))
Min. measuring span
5 or 25 Ω (see table in chapter Digital measuring
Characteristic curve
Linear to resistance or special characteristic
curve
1)
Prerequisites: same resistance for all three lines.
Summary of Contents for sitrans tr300
Page 7: ...Table of contents SITRANS TR200 TR300 6 Operating Instructions 06 2010 A5E01071992 03 ...
Page 21: ...Installation SITRANS TR200 TR300 20 Operating Instructions 06 2010 A5E01071992 03 ...
Page 69: ...Service and maintenance SITRANS TR200 TR300 68 Operating Instructions 06 2010 A5E01071992 03 ...
Page 81: ...Dimension drawings SITRANS TR200 TR300 80 Operating Instructions 06 2010 A5E01071992 03 ...
Page 93: ...Glossary SITRANS TR200 TR300 92 Operating Instructions 06 2010 A5E01071992 03 ...