5.1 Safety notes on connection
SITRANS TR200/TR300
Operating Instructions, 06/2010, A5E01071992-03
23
Zone 1 in type of protection "i" - intrinsic safety
● Only connect the transmitter, in accordance with the certificate of compliance, to devices
certified as intrinsically-safe.
Maximum values of the auxiliary power supply and signal circuits:
U
i
= DC 30 V
I
i
= 100 mA
P
i
= 750 mW
L
i
= 2 μH
C
i
= 13 nF
Maximum values of the sensor circuit:
U
0
=DC 6 V:
I
0
= 25 mA
P
0
= 37 mW
L
0
[mH]
50
10
1
0,1
C
0
[μF]
1
1,6
2,6
4,8
Zone 2 in type of protection "ic" - device connection through intrinsic safety
● Install the transmitter in a housing to degree of protection IP54 according to EN 60529.
● Connect the transmitter only to devices that have been approved as "ic" certified devices
(device protection through intrinsic safety) in category 3.
● Be sure to observe the respective values.
Maximum values of the auxiliary power supply and signal circuits:
U
i
= DC 30 V
I
i
= 100 mA
P
i
= 750 mW
L
i
= 2 μH
C
i
= 13 nF
Zone 2 in type of protection "nA" - non-sparking resources
● Install the transmitter in a housing to degree of protection IP54 according to EN 60529.
● Adhere to the conditions for installers applicable to this type of protection.
● The maximum approved input voltage is U
n
= 32 V DC.
● Take measures to ensure that the supply voltage (including transients) does not rise
above 140 % of the rated voltage.
Additional requirements for use in dust explosion protected areas
Install the transmitter in an enclosure suitable for the respective type of dust and
corresponding Zone in accordance with the inspection certificate valid in your country.
Summary of Contents for sitrans tr300
Page 7: ...Table of contents SITRANS TR200 TR300 6 Operating Instructions 06 2010 A5E01071992 03 ...
Page 21: ...Installation SITRANS TR200 TR300 20 Operating Instructions 06 2010 A5E01071992 03 ...
Page 69: ...Service and maintenance SITRANS TR200 TR300 68 Operating Instructions 06 2010 A5E01071992 03 ...
Page 81: ...Dimension drawings SITRANS TR200 TR300 80 Operating Instructions 06 2010 A5E01071992 03 ...
Page 93: ...Glossary SITRANS TR200 TR300 92 Operating Instructions 06 2010 A5E01071992 03 ...