99
PBD-51041066
SITRANS LG270 - Operating Instructions
44295-EN-140321
ScadaPack
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
3
2
13
45
5
2
1
3
4
9
6
7
8
2o
ff
on
( )
()
(-)
(-)
+8
+30 Vdc
to
GND
COM Part 3 (C3)
RS485
TXD-
TXD+
GND
Fig. 57: Connection of SITRANS LG270 to RTU ScadaPack
1 SITRANS LG270
2 RTU ScadaPack
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Floating Point
Input Register Base Number
30001
The basic number of the input registers is always added to the input register address of SITRANS
LG270.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.