Factory settings
B.1 Transmitter factory settings
92
Menu item
Parameter
Factory
settings
Options
More info
Digital output
Pulse
Error, direction/limit, batch, frequency, pulse, error
number, off
(Page 78)
Relay output
Error level
Error, direction/limit, cleaning, error number, off
(Page 78)
Direction/limit
switch
Off
1 setpoint, 2 setpoints
Setpoints
0%
-100 ... +100%
Hysteresis
5%
0.0 ... 100%
Batch
Off
(Page 79)
Batch quantity
0
Sensor size dependent
Batch
compensation
0
-100 ... +100 m
3
Batch counter
Down
Up, down
Frequency
Off
500 Hz, 1 kHz, 5 kHz, 10 kHz
(Page 78)
Time constant
5 s
0.1 ... 30 s
Pulse
On
(Page 78)
Pulse polarity
Positive
Positive, negative
Pulse width
66 ms
64 μs 130 μs, 260 μs, 510 μs, 1.0 ms, 2.0 ms, 4.1
ms, 8.2 ms, 16 ms, 33, ms, 66 ms, 130 ms, 260
ms, 520 ms, 1.0 s, 2.1 s, 4.2 s
Volume/pulse
Sensor size
dependent
Dimension-dependent
Time constant
0.1 s
0.1 ... 30 s
External input
External input
Off
Batch, reset totalizer, freeze output, forced output,
off
(Page 80)
Batch
Start
Start, hold/continue, stop, Qmax 2
www.eltra-trade.com [email protected]
+421 552 601 099
Summary of Contents for SITRANS F M MAG 5000
Page 1: ...SITRANS F M MAG 5000 6000 Manual www eltra trade com info eltra trade com 421 552 601 099 ...
Page 9: ...Table of contents 6 www eltra trade com info eltra trade com 421 552 601 099 ...
Page 93: ......
Page 103: ...www eltra trade com info eltra trade com 421 552 601 099 ...
Page 105: ...Approvals Certificates 102 www eltra trade com info eltra trade com 421 552 601 099 ...