Technical data
6.2 Output
SITOP SEL1200-1400
38
Manual, 06.2019, A5E46496083-1-76
6.2
Output
6EP4438-7FB00-3DX0
6EP4438-7EB00-3DX0
Output
Regulated DC voltage
Output voltage
U
out
= U
in
- approx. 0.5 V
Total tolerance
Corresponding to the supplying input voltage
Number of outputs
8
Output current up to 60 °C for each output (rated value)
•
Remark
10 A (in total, not more than 60 A)
60 ... 70 °C derating: 2 % I
out
/K
Adjustable response threshold
2 - 10 A
Connecting outputs in parallel
Yes, max. 4 × 2 outputs each that must lie next to one another.
Switching on outputs
All outputs are switched-on after the supply voltage ramps up
> 20 V, delay time of 25 ms, 200 ms, 500 ms – or "load opti-
mized", selectable using DIP switch.
Shutdown characteristics:
Figure 6-1
Shutdown characteristic
The following applies for the SEL1200: In the range > 150 %, a higher current is briefly
permitted; afterwards it is shut down corresponding to the "Shutdown characteristic"
diagram.